Troubleshooting – Comfort-Aire PTHP15A130A User Manual

Page 14

Advertising
background image

PACKAGED TERMINAL

OWNER’S MaNual

Heat Controller

13

TROUBLESHOOTING

POSSIBLE CAUSES

SOLUTIONS

UNIT DOES NOT START

• Unit may be unplugged

• Fuse may have blown

• Circuit breaker may have tripped

• Unit may be off or in wall thermostat mode.

Check section on dipswitch settings to verify dipswitches

are set properly.

• Unit may be in a protection or diagnostic failure mode. See

section on diagnostic codes.

• Check that plug is plugged securely in wall receptacle.

Note: Plug has a test/reset button on it. Make sure that the

plug has not tripped.

• Replace the fuse.

• Reset circuit breaker.

• Turn unit on (bottom right button on keypad).

Note: lf the unit turns on, the LED will be green. If the unit is off,

the LED will be red. If there is no LED on, there is a problem

with power or damage to the control.

DISPLAY HAS STRANGE NUMBERS/CHARACTERS ON IT

• The unit may be in a diagnostic condition. Check diagnostic

codes --- checking Control section to determine if unit has had

a failure.

• The unit may be set for °C (instead of °F), see the

SET UP

OPERATION.

UNIT MAKING NOISES

• Clicking, gurgling and whooshing noises are normal during

operation of unit.

UNIT NOT COOLING / HEATING ROOM

• Unit air discharge section is blocked

• Temperature setting is not high or low enough

Note: Setpoint limits may not allow the unit to heat or cool the

room to the temperature desired. Check section on dipswitch

settings.

• Unit air filters are dirty.

• Room is excessively hot or cold when unit is started

• Vent door left open

• Unit may be in a protection or diagnostic failure mode. Check

section on Intelligent Self --- checking Control.

• Compressor is in time delay. There is a protective time delay

(approx. 3 minutes) on starting the compressor after a power

outage (or restarting after it has been turned off), to prevent

tripping of the compressor overload.

• Make sure that curtains, blinds or furniture are not restricting

or blocking unit airflow.

• Reset to a lower or higher temperature setting.

• Remove and clean filters.

• Allow sufficient amount of lime for unit to heat or cool

the room. Start heating or cooling early before outdoor

temperature, cooking heat or gatherings of people make room

uncomfortable.

• Close vent door.

• Check dipswitch settings for desired comfort.

• Wait approximately 3 minutes for compressor to start

WATER DRIPPING INSIDE

WATER DRIPPING INSIDE

• Wall sleeve is not installed level

ICE OR FROST FORMS ON INDOOR COIL

• Low outdoor temperature

• Dirty filters

COMPRESSOR PROTECTION

• Power may have cycled, so compressor is in a restart

protection.

• Random Compressor restart-Whenever the unit is plugged in,

or power has been restarted, a random compressor restart will

occur. After a power outage, the compressor will restart after

approximately 3 minutes.

• Compressor Protection-To prevent short cycling of the

compressor, there is a startup delay of 3 minutes and a

minimum compressor run time of 3 minutes.

• When outdoor temperature is approximately 55°F (12.8 °C) or

below, frost may form on the indoor coil when unit is in Cooling

mode. Switch unit to FAN operation until ice or frost meIts.

• Remove and clean filters.

• Wall sleeve must be installed level for proper drainage of

condensation. Check that installation is level and make any

necessary adjustments.

• If a drain kit has not been installed, condensation runoff during

very hot and humid weather is normal. See Note 2. If a drain

kit has been installed and is connected to a drain system,

check gaskets and fittings around drain for leaks and plugs.

Advertising