Operation, Display interface (ap7862j only) – American Power Conversion AP7862J User Manual

Page 11

Advertising
background image

Basic and Metered Rack Power Distribution Unit

7

Operation

Display interface
(AP7862J only)

Link - Rx/Tx

10 /100

Status

Serial Port

Reset

Press to

select line.

Press and hold

to invert display.

- Warning

- OK

- Overload





  

L3

L2

L1

Am

ps

Am

ps









Phase Indicator

LED

s:

• Indicates the phase corresponding to the current listed in the digital

display.

• Indicates normal (green), warning (yellow) or alarm (red)

condition.



Control button:
• Press to change the phase of the current displayed on the digital

display.

• Press and hold for five seconds to view the orientation; hold for an

additional five seconds to change the orientation.

• Press to silence an alarm.



Ethernet port: Connects the PDU to your network, using a CAT5
network cable.



Status

LED

: Indicates the status of the ethernet LAN connection and

the state of the

Metered

PDU.



Link

LED

: Indicates whether there is activity on the network.



Serial port: Access internal menus by connecting this port (

RJ

-

11

modular port) to a serial port on your computer, using the supplied
serial cable (part number

940

-

0144

).



Display of the current used by the PDU and attached devices:
• Shows the aggregate current for the phase corresponding to the

Phase Indicator

LED

that is illuminated.

• Cycles through all three phases in 3-second intervals.



Reset switch: Resets the PDU to its default settings.

Advertising