Figure 12

CHASE AIR INTAKE

WITH RODENT GUARD

PROVIDES A 6"

DIAMETER OPENING

FOR VENTILATION INTO

CHASE.

the chimney Tee with the Tee Support as

detailed in the full DuraPlus HTC installation

instructions. Continue to install the remainder

of the chimney system as described in those

installation instructions.

Step 6. Ensure CAS system has access to

outside air. The CAS system needs to have

access to outside air for the stove to use. If

the chimney is unenclosed on the outside of

the home, no steps are needed to provide air.

The outside portion of the CAS Wall Thimble

has air-inlet openings to provide air to the

stove. However, if the chimney is enclosed in

a chase, the chase needs to have ventilation

to supply air for the CAS system. This opening

can be provided by the Chase Air Intake with

Rodent Guard (Fig 12) or by a small opening

in the chase that provides a minimum of 12

square inches of free area (opening can be

louvered or covered with mesh screen).

Step 7. Continue to install remainder of the

chimney system according to the complete

DuraPlus HTC installation instructions; L170

DuraPlus HTC Installation Instructions.