Zc kit – large pellet insert – Travis ZC Kit – Large Pellet User Manual

Page 3

Advertising
background image

ZC Kit – Large Pellet Insert

(99200149)

Page 3 of 8

10/9/06

© Travis Industries, Inc.

Vent Termination Requirements (See the illustration below)

•

Must have an approved cap (to prevent water from entering) or a 45° downturn.

•

If the termination is located on a windy side of the house, an approved house shield is

recommended to prevent soot from building up on the side of the house.

•

Must not be located where it will become plugged by snow or other material.

•

Horizontal terminations must protrude 12" from the wall, vertical terminations require 24".

H

G

A

D

F

NOTE: Measure clearances to the nearest edge of the exhaust hood.

A

E

B

C

F

X

A

Minimum 4' clearance below or beside any door or window that opens

B

Minimum 1' clearance above any door or window that opens

C

Minimum 2' clearance from any adjacent building

D

Minimum 7' clearance above any grade when adjacent to public walkways

NOTE: Vent may not terminate in covered walkway or breezeway.

E

Minimum 2' clearance above any grass, plants, or other combustible materials

F

Minimum 3' clearance from any forced air intake of any other appliance

G

Minimum 2' clearance below eaves or overhangs

H

Minimum 1' clearance horizontally from combustible wall

X

Must be a minimum of 2' above the roof