WIKA operating instructions pressure transmitter, model MG-1

11609681.02 03/2013 GB/D/F/E

GB

6. Commissioning, operation

6. Commissioning, operation

Required tool: SW 24 open-ended spanner

WARNING!

Prior to commissioning, the pressure transmitter must be subjected to a visual

inspection.

Only use the pressure transmitter if it is in perfect condition with respect to safety.

Making the mechanical connection

■

To ensure that the wetted parts do not get soiled, the protection

cap should not be removed until immediately prior to mounting.

■

Use only BAM-certified gaskets.

■

During mounting, make sure that the sealing faces at the pressure

transmitter and the measuring point are clean and undamaged.

■

Only ever screw in, or unscrew, the pressure transmitter to the

prescribed torque via the spanner-flats, and using tools which are

appropriate and clean for use with oxygen.

The correct torque depends on the dimensions of the process

connection and the gasket used (form/material). When screwing

in or unscrewing the pressure transmitter, do not use the housing or plug for purchase.

■

When screwing in, do not cross the threads.

■

Only lubricate thread with materials approved for use with oxygen.

■

For information on tapped holes and welding sockets, please refer to our Technical Information

IN 00.14 at www.wika.com.

max.

20 Nm