Gb 6. commissioning, operation – WIKA OT-1 User Manual

Page 11

Advertising
background image

11

WIKA operating instructions OEM pressure transmitter, model OT-1

2127027.02 09/2013 GB/D/F/E

GB

6. Commissioning, operation

6.2 Electrical mounting
6.2.1 Connection assembly

■

Use the pressure transmitter with shielded cable. The cable shield must be grounded, if the cable is longer than

30 m or leaves the building.

■

Use a cable with suitable characteristics for the particular operating conditions.

■

For cable variants, strain relief must be employed.

■

Cable with ventilation tubes must be vented to atmosphere.

■

The instrument must be grounded via the process connection.

■

Select a cable diameter that matches the cable gland of the plug. Make sure that the cable gland of the mounted

plug has a tight fit and that the seals are present and undamaged. Tighten the threaded connection and check that

the seal is correctly seated, in order to ensure the ingress protection.

■

For cable outlets, make sure that no moisture enters at the cable end.

■

This equipment is intended for operation with low voltages, which are separated from the power supply or voltages

of greater than AC 50 V or DC 120 V. Preferably, a connection to an SELV circuit is recommended, or alternatively to

circuits with a different protective measure in accordance with IEC 60364-4-41.

6.2.2 Connection diagrams

Circular connector M12 x 1 (4-pin)

2-wire

3-wire

4

3

1

2

U

+

1

1

U-

3

3

S

+

-

4

U+

Positive power supply

U-

Negative power supply, reference potential

S+

Positive output terminal

2-wire

The two connection lines are used for the voltage supply.

The measurement signal also provides the supply current.

3-wire

Two connection lines are used for the voltage supply.

One connection line is used for the measurement signal.

Cable outlet

2-wire

3-wire

U

+

brown

brown

U-

green

blue

S

+

-

white

Metri-Pack series 150 (3-pin)

2-wire

3-wire

U

+

B

B

U-

A

A

S

+

-

C