Safety – WIKA S-20 User Manual

Page 9

Advertising
background image

9

GB

WIKA Safety manual pressure transmitter, model S-20

14082128.02 06/2014 GB/D/F/E

2.5 Description of the safety function and diagnosis

The safety function of the model S-20 is that the pressure transmitter converts the physical input parameter of pressure

into an electrical signal.

■

The model S-20 recognises the following error states

Error detection

Output signal
4 ... 20 mA

(2-wire)

20 … 4 mA

(2-wire)

DC 1 … 5 V

DC 1 … 6 V

DC 0.5 … 4.5 V DC 0.5 … 4.5 V

ratiometric

Cyclical testing
Underpressure from which

on the error is detected

-2.5 %

Low alarm value

max. 3.6 mA

-6.25 %

Low alarm value

max. 3.6 mA

-12.5 %

Low alarm value

0.2 … 0.5 V

-10 %

Low alarm value

0.2 … 0.5

-5 %

Low alarm value

0.1 … 0.3 V

-5 %

Low alarm value

0.1 … 0.3 V

Overpressure from which on

the error is detected

+6.25%

Low alarm value

max. 3.6 mA

+2.5 %

Low alarm value

max. 3.6 mA

+25 %

Low alarm value

0.2 … 0.5 V

+20 %

Low alarm value

0.2 … 0.5 V

+10 %

Low alarm value

0.1 … 0.3 V

+10 %

Low alarm value

0.1 … 0.3 V

ADC communication error

(within the instrument)

Low alarm value

max. 3.6 mA

Low alarm value

max. 3.6 mA

Low alarm value

0.2 … 0.5 V

Low alarm value

0.2 … 0.5 V

Low alarm value

0.1 … 0.3 V

Low alarm value

0.1 … 0.3 V

Testing on switch-on
Sensor error, EEPROM

checksum error (hardware

error detected by

instrument)

Low alarm value

max. 3.6 mA

Low alarm value

max. 3.6 mA

Low alarm value

0.2 … 0.5 V

Low alarm value

0.2 … 0.5 V

Low alarm value

0.1 … 0.3 V

Low alarm value

0.1 … 0.3 V

Table 2-2: Error detection

■

All failures detected are indicated as downscale alarm signals (low alarm values).

■

Undetected errors can generate an undefined output signal within or outside of the span range.

■

The alarm signal for over- or underpressure is triggered when the error condition exists uninterrupted for a minimum

of 10 seconds.

■

Errors which are checked cyclically are not permanently active, i.e. a reentry into measuring mode after exiting the

error range is possible during running.

■

Missing short-circuit resistance between signals in accordance with table 2-1: Parameters can lead to the destruc-

tion of the pressure measuring instrument. Short circuit leads to the loss of the safety function.

■

The external supervisory logic unit must bring the plant to a safe state if the alarm condition is entered.

2. Safety