6

2089436.03 12/2010 GB/D/F/E

GB

WIKA operating instructions pressure gauge model 6 per ATEX

2.3 Safety instructions for pressure gauges per ATEX

WARNING!

Non-observance of these instructions and their contents may

result in the loss of explosion protection.

WARNING!

It is imperative that the application conditions and safety require-

ments of the EC-type examination certificate are

followed.

Pressure gauges must be earthed via the process connection!

Technical data
Operating temperature

Ambient: -20 ... +60 °C (optional: -40 … +60 °C)

Medium: The permissible medium temperature does not only depend on the

instrument design, but also on the ignition temperature of the surroun-

ding gases, vapours or dust. Both aspects have to be taken into account.

For permissible maximum medium temperatures see table 1.

Attention! With gaseous substances, the temperature may increase as a result

of compression warming. In such cases the rate of change of pressure must be

slowed down or the permissible medium temperature must be reduced.

Table 1: Permissible medium temperature

2. Safety

Temperature class of the

ambient atmosphere

(ignition temperature)

Maximum permissible medium temperature

(in the measuring system)

T 6 (> 85 °C)

+70 °C

T 5 (> 100 °C)

+80 °C

T 4 (> 135 °C)

+80 °C

T 3 (> 200 °C)

+80 °C

T 2 (> 300 °C)

+80 °C

T 1 (> 450 °C)

+80 °C