Approvals – Pfannenberg PATROL PA X 20 Series User Manual
Page 7

085 501 946j
30305-004j
7
Approvals
(valid for marked equipment)
Construction
Product Directive
(89/106/EWG)
PA10/ PA 20, 110-230V AC:
PA10/ PA 20, 24-48V DC:
PA10-SSM, PA 20-SSM:
VdS 0786-CPD- 21184
VdS 0786-CPD- 21223
0786-CPD- 21224
PA 10/ PA 20
Options
–SSM
Rated voltage
24 – 48 V DC
110V – 240V AC
Operating voltage range acc.
to EN54-3, EN54-23
18V – 60V
Option: -SSM (18V – 30V)
95V – 265V AC
Tone
2
15
60
104
131
146
Compliant with the Construction Product Directive (89/106/EWG)
1200Hz-500Hz (Saw tooth) DIN/PFEER P.T.A.P.
500Hz-1200Hz (Slow whoop)
825Hz (Continuous)
660Hz (Intermittent tone)
800Hz/ 1000Hz (Alternating tone)
544Hz/ 440Hz (NF S 32-001)
Signaling area
EN54-3: see documents 30305-005-1
(PA 10)
and 30306-005-1
(PA 20)
Environmental protection class
Type B
The test was performed using the provided diaphragm nipples and the outer fixing holes.
VdS
PA10 / PA 20, 110 – 230V AC:
PA10/ PA 20, 24 - 48V DC:
PA10-SSM, PA 20-SSM:
G212116
G212191
G212192
Data see Construction Product Directive (89/106/EWG)
GL
GLxxxxx (in preparation) Environmental Category C, H, EMC1
UL, cUL
Rated voltage
Audible Signal Appliance
Fire Alarm Equipment
ULSZ, ULSZ7
Audible and Visual Signal Appliance
General Signal Equipment
UCST, UCST7 and UEES, UEES7
PA 10
PA 20
24V – 48V DC
(Fire Alarm Equipment)
12V – 48V DC
(General Signal Equipment)
x
Special application, limited operating
voltage range 18 – 60V DC
x
PA 10
PA 20
24V AC
110 – 240V AC
-
x
PA X 10 ..
PA X 20 ..
115V AC
230V AC
24V AC
12V DC
24V DC
48V DC
-
x
PATROL sounders and combined units PA 10/ PA 20/ PA X 10../ PA X 20.. comply with the limits for a Class B digital
device, pursuant to part 15 of the FCC Rules.
UL/ cUL specifications:
Inrush current
PA 10, PA 20
Surge Current Peak
Surge Current RMS (16,7ms frame)
Voltage
24 – 48 V DC
27 A
4,5 A
60 V DC
24 V AC
11,5 A
6,8 A
30 V AC
110 – 240 V AC
18,5 A
1,45 A
265 V AC
Suitable for indoor and outdoor use.
Signaling area: see document 30305-005-1 (PA 10) and 30306-005-1 (PA 20)
Cable gland entries:
Conduit installation needs to be UL/ cUL listed fittings suitable for knockout openings. The supply wiring has to be enclosed in metal
conduits for products for Fire Alarm Use.
Installation:
The units shall be installed indoors or outdoors in accordance with the manufacturer’s installation instructions as well as the National
Electrical Code (NFPA 70) and the National Fire Alarm Code (NFPA 72) for the units evaluated for Public Fire Alarm applications in the
U.S. In Canada, they shall be installed in accordance with the Canadian Electrical Code, Part 1 and the Standard for the Installation of
Fire Alarm Systems CAN/ULC-S524-M91 for the units evaluated for Public Fire Alarm applications. The installation shall also be in a
manner acceptable with the local authority having jurisdiction.
For audible application for Fire Alarm Service use both terminals for connection. Break wire run to provide Electrical Supervision (see
UL 464 clause 39.1e). The tone no. 111 is to be used for evacuation use only (see UL 464 clause 39.1e)
Volume control:
PA 20/ PA X 20 ..: The volume control has to be set to the secured factory position.
cUL directional characteristics for
the horn:
AXIS
ANGLE
dBA
Horizontal
32 deg. left or right
-3
Horizontal
28 deg. left or right
-6
Vertical
32 deg. left or right
-3
Vertical
28 deg. left or right
-6
Min. Output sound pressure
level: [dB(A)]
(Tone no. 2, 15, 60, 104, 131, 146, 111,
112, and 113 was used for this test.)
Type
Voltage
UL 464 db(A) at 10 ft ++
CAN/ULc-S525-07
PA 10 (24-48 DC)
18V DC
82,4 (for tone 113)
92,4 (for tone 111)
PA 20 (24-48 DC)
18V DC
84,3 (for tone 113)
99,3 (for tone 111)
Connecting cables:
7 [0.28"]
7 [0.28"]
solid
stranded