OPERATION AND INSTALLATION INSTRUCTIONS

Industrial Control Panel / Enclosure Heaters

INSTALLATION
A.1
The industrial control panel enclosure heater is fan
forced, and designed to maintain a suitable temperature inside
a control panel or metal enclosure.
A.2 The following factors must be taken into consideration
when selecting the proper heater; surface area, insulation
properties, enclosure location, and difference in temperature
between the ambient and the enclosure.
A.3 The intended use of the heating unit is to protect against
the effect of low temperatures, such as freezing and
condensation from damaging critical components inside a
control enclosure.

A.4 The heater unit is not designed for use as a comfort or
space heater and should not be installed in hazardous,
corrosive, dusty, or wet environments.
A.5 Operating surface temperatures of these heaters is
substantial enough to cause burns upon contact with bare skin.
A.6 Before servicing, ensure to disconnect the heater from
the supplied power and allow approximately 10 to 15 minutes
for the heater unit to cool.

MOUNTING AND WIRING
B.1
The heater is to be mounted inside a metal enclosure on
a metal surface only and should be mounted in the center of
the enclosure as low as possible for best heat distribution.
B.2 The heater is to be mounted in a vertical position as
intended, so the wiring terminal block is at the bottom, and the
heated air discharge vents are at the top. Mount the heater to
the enclosure or control panel using four #10 metal screws.

B.3 In order to ensure unrestricted airflow through the
enclosure heater and avoid high temperatures on surrounding
surfaces, heat sensitive components should be positioned
away from the heated air discharge vents as shown below.

B.4 Disconnect power before installation or servicing the
heater.
B.5 The heater must be wired by qualified personnel to the
applicable local electric code requirements. Please note that
the heater does not have an OFF position, so to fully shut
down the heater; power must be disconnected from the supply.
B.6 Check the supply voltage requirements with the heater
label voltage rating prior to installation. Use wires suitable for
no less than a temperature rating of 90°C.

OVERHEAT PROTECTION
C.1
The enclosure heaters are equipped with a temperature
limit switch. In the event of fan failure or an overheat condition,
the automatic reset temperature limit switch will open, breaking
power to the heating element.

OPERATION AND MAINTENANCE
D.1
Apply power to the heating unit by way of the terminal
block as indicated and then set the thermostat to the desired
temperature for the enclosure or control panel.
D.2 Please allow a suitable amount of time for the thermostat
to cycle and the temperature in the enclosure to stabilize. Due
to system variances, you may need to re-adjust the thermostat
to achieve the desired temperature.
D.3 The internal fan motor has permanently lubricated
bearings and should not require maintenance.
D.4 To achieve proper airflow through the heater unit, ensure
to periodically check and clean the air vent openings from any
dust or debris.
D.5 The enclosure heaters have a built in indicator light to
indicate when the heat is on, and equipped with a switch
function which will allow the fan to run continuously for more
uniform temperature distribution.
D.6 In “FAN” mode the fan will run continuously, and the
heater unit will still provide heat when the temperature drops
below the set point on the thermostat. In ”AUTO” mode the fan
will cycle on only when the heating element is energized.