Installation of grade d and e systems, Power source, Radio linked systems – Aico Residential Fire Detection RFD User Manual

Page 16: Audibility, Special needs provision

Advertising
background image

16

In the event of a fire being detected, a

small vibrating pad located beneath the

sleeper’s pillow gently alerts them. At the

same time a powerful strobe light flashes

to provide a further visual warning.

Devices such as these are now

increasingly cited as important

considerations and should be considered

as a matter of course in applications

where the residents are likely to be

elderly, as in a nursing home for example,

or in sheltered accommodation.

The 2004 Code notes that the final system

applied should take into account the

assessed needs of the person being

protected. However, it should always

conform to BS 5446: Pt.3 (Grade A and B

systems aside, where other standards

quoted may be more appropriate).

INSTALLATION OF GRADE

D AND E SYSTEMS

Once these considerations have all

been taken into account and the

system adequately planned, it can then

be installed, tested and commissioned.

Systems should be installed in

accordance with BS 7671 (IEE

Regulations 16th Edition) by a qualified

installer. All alarms should be fitted into

place securely and permanently, and

attention given to protecting all wiring

from impact or rodent damage by

recessing or trunking.

If you intend to install the alarms in a new

building, however, it is usually necessary to

wait until all other work on site has been

completed and the building has been

fully cleaned before installing any smoke

alarms. This is because excess dust and

debris from building work can

contaminate the alarms and render them

prone to false alarms. However, new ‘Easi-

fit’ style alarms are a useful exception,

with the wiring able to be completed

during ‘first fix’ and the detector head

simply slotted into place when all

cleaning work has been completed.

If, for any reason, other types of alarms

have to be installed before all work is

complete, ensure that they are

completely covered, particularly around

the edges, with the dust cover that should

be supplied with each alarm. Only when

all cleaning is finished should these dust

covers be removed.

POWER SOURCE

The normal supply for Grade D and E

systems is the public mains supply. A Grade

D system should be connected either to an

independent circuit at the dwelling’s main

distribution board (with no other electrical

equipment attached except for a

dedicated monitoring device) or a

separate, electrically protected, regularly

used local lighting circuit. A Grade E

system may only use the former option.

Hard wired interconnected smoke alarms

should be on one final circuit. However, the

2004 version of the code now accepts

that smoke and heat alarms using a radio

signal for the interconnect can be

separately wired from the nearest lighting

circuit with a permanent mains supply.

RADIO LINKED SYSTEMS

Pages 41-44 of the 2004 Code now set out

the criteria for radio-linked systems. It is

acknowledged now that Grades D-F systems

may use radio interconnection. However, it

warns about the potential drawbacks of

battery powered units being interconnected

in such a way if there is a need to replace

the batteries at regular intervals (by

implication mains powered radio-linked

alarms do not have these drawbacks).

As is typical with the Code, it stresses the

need to ensure that such a system meets

the needs of the application.

The new publication also goes out of its

way to recognise that the old Code

AUDIBILITY

Audibility is another factor to be

considered. The Code comments that

ideally, an alarm system should be

capable of producing a sound level of

75dB(A) at the bedhead, but that this

is unlikely to be achieved unless there

is a sounder/smoke alarm in the

bedroom itself. As there is no evidence

of life being lost in single family

dwellings due to the lower sound level

achieved by siting an alarm within 3

metres of the bedroom doors, in many

dwellings this would be acceptable. In

HMOs, where higher levels of ambient

noise is likely, additional

alarms/sounders may be necessary.

A practical way to check audibility is with

the alarm sounding in its intended

location, check that the occupant is able

to hear it in each bedroom with the door

closed above the sound of a radio set to

a reasonably loud conversation level. In

this case, interconnected alarms provide

an ideal solution, a remote alarm picking

up the fire and a sounder being triggered

to wake the occupier.

SPECIAL NEEDS

PROVISION

Back in 1995, the original Code

acknowledged the special needs of

people who are deaf or hearing

impaired and recommended the use of

alternative fire alarm systems to meet

their needs. More attention is paid to the

issue in the new 2004 update.

A special alarm can be incorporated

into domestic mains fire alarm systems

to protect people with impaired

hearing. It’s a simple, yet ingenious idea.

Advertising