American Power Conversion MX28B200 User Manual

Page 39

Advertising
background image

MX28B200/400 –48 VDC User’s Manual (990-9133)

Page 33

PARAMETER NAME/

[MENU LOCATION]

DESCRIPTION

DISPLAY SCREENS /

DEFAULT SETTINGS

OEM S Offset
Security Level {2}
[OEM]

Current offset adjustment for factory
calibration of battery current
readings/settings.

OEM S Offset m+
0.0 A

Output Relay 1 Alarm
Security Level {1}
[SYSTEM/OUT-RLY/RLY-
MAP]
•
•
•
Output Relay 6 Alarm
Security Level {1}
[SYSTEM/OUT-RLY/RLY-
MAP]

Output Relay 1 Alarm can be “mapped”
to activate other output relays (“Ignore”
activates no additional relays).

•
•
•
Output Relay 6 Alarm can be “mapped”
to activate other output relays (“Ignore”
activates no additional relays).

Out-Rly 1 Alm m+
Ignore

•
•
•
Out-Rly 6 Alm m+
Ignore

Output Relay 1 Alias
Security Level {1}
[SYSTEM/OUT-RLY/ALIAS]
•
•
•
Output Relay 6 Alias {1}
[SYSTEM/OUT-RLY/ALIAS]

An alternate name (alias) can be
assigned to Output Relay 1 if desired.
•
•
•
An alternate name (alias) can be
assigned to Output Relay 6 if desired.

Out-Rly 1 m+
Relay 1
•

•
•
Out-Rly 6 m+
Relay 6

Output Relay 1 Delay
Security Level {1}
[SYSTEM/OUT-RLY/RLY-
MAP]
•
•
•
Output Relay 6 Delay
Security Level {1}
[SYSTEM/OUT-RLY/RLY-
MAP]

Delay between sensing of the alarm
condition and activation of Output Relay
1. An alarm condition must exist for
longer than the delay to be activated.
•
•
Delay between sensing of the alarm
condition and activation of Output Relay
6. An alarm condition must exist for
longer than the delay to be activated.

Out-Rly 1 Dly m+
0 sec

•

•
•
Out-Rly 6 Dly m+
0 sec

Output Relay Major Alias
Security Level {1}
[SYSTEM/OUT-RLY/ALIAS]

An alternate name (alias) can be
assigned to the major Relay if desired.

Relay Major
m+
Major

Output Relay Minor Alias
Security Level {1}
[SYSTEM/OUT-RLY/ALIAS]

An alternate name (alias) can be
assigned to the Minor Relay if desired.

Relay Minor
m+
Minor

PIN 1 change
Security Level {2}
[SYSTEM/SETUP]

Permanently change password (PIN) that
permits security Level 1 parameter
changes - limited access.

PIN m+

1111

PIN 2 Change
Security Level {2}
[SYSTEM/SETUP]

Permanently change password (PIN) that
permits security Level 2 parameter
changes - unlimited access.

PIN 2 m+

2222

Advertising