Step 3: install the web/snmp management card, Step 3: install the web/snmp management card 8, Continue d – APC AP9606 User Manual

Page 12: Expansion/triple chassis installation

Advertising
background image

8

Expansion/Triple Chassis Installation

continued

Step 3: Install
the Web/SNMP
Management
Card

Caution: If the UPS uses more than one APC management

peripheral, see the supplied Installation of Multiple
SmartSlot Cards
sheet. You must install the APC
peripherals in the correct order, otherwise the
peripherals may fail to operate properly.

1. If PowerChute plus is installed, stop the PowerChute plus

service and disconnect its cable from the UPS serial port.

2. Use the screws that hold the expansion slot cover in place

to secure the Management Card in the chassis slot.

3. Connect a network interface cable to the Management

Card’s 10Base-T network connector.

4. If you are using the optional AC Adapter (AP9505), do

the following:

a. Connect the adapter to the chassis.

b. Connect the adapter to an independent AC input so that

the Management Card can continue to operate if the
UPS is turned off or fails.

5. If neccessary, reconnect the PowerChute plus cable.

6. If neccessary, restart the PowerChute plus service.

7. See “Quick Configuration” on page 9.