Troubleshooting, Dépannage – Briggs & Stratton 100 Amp Automatic Transfer Switch User Manual

Page 11

Advertising
background image

11

Troubleshooting

Problem

Cause

Correction

Automatic transfer switch does not
transfer to generator

1. Generator breaker open.

2. Generator voltage not acceptable.

1. Reset generator circuit breaker.

2. Refer to generator manual.

Automatic transfer switch does not
transfer to utility

1. Service disconnect breaker open.

2. Utility voltage not acceptable.

1. Reset service disconnect breaker.

2. Wait for utility voltage to return to

normal.

Generator is still running after switch
transfers to utility power

Engine cool down period.

Engine should stop after 1 minute.

Generator or supervised loads (air
conditioner, etc.) are operating
improperly when generator is supplying
power

1. A-A or B-B contacts not operating

correctly.

2. Too much load on generator.

3. Current transformer not connected.

4. Broken current transformer.

1. Check A-A or B-B contacts for

proper operation and/or check
control wiring to external load.

2. Decrease load to generator.

3. Plug CT connectors into control

module.

4. Contact local Briggs & Stratton

service center.

Generator is still running after utility
power is restored

1. Minimum engine run time has not

elapsed.

2. Fuse(s) in transfer switch is

defective.

1. Wait five minutes for transfer

switch to retransfer to utility power.

2. Check fuse(s) and replace if

necessary.