COOLING LOAD BTU

The cooling load chart shows loads in Btuh as well. To use the cooling load chart, first find the design enthalpy from a
psychrometric chart using the design dry bulb and wet bulb temperatures. (See psychrometric chart on p. 11.) The
cooling load can then be found for a range of enthalpies for each ventilator.

EXAMPLE:

The cooling design dry bulb temperature for Milwaukee, WI is 87°F and the average wet bulb at that
temperature is 73°F. On the psychrometric chart the enthalpy is about 37.7 Btu/lb of dry air which will round
up to 38 Btu/lb of dry air. In the left column, at 38 Btu/lb the HRVBBLHU1250 would have an additional
cooling load of 6428 Btuh. This additional load should be taken into account when sizing the air cooling
equipment.

Outside

Enthalpy

Btu/lb

Cooling Load (Btuh) @ Inside Design Temp 75°F and 50% Relative Humidity

HRVBBLHU1150 HRVBBLHU1250 HRVBBSVC1150 HRVBBSVC1200

HRVBBLVU1150

HRVBBLVU1200

HRVBBLVU1330

30

670

1,071

780

990

770

990

1,390

31

1,090

1,741

1,300

1,650

1,290

1,650

2,310

32

1,509

2,411

1,820

2,310

1,800

2,310

3,240

33

1,928

3,080

2,340

2,970

2,310

2,970

4,170

34

2,347

3,750

2,860

3,630

2,830

3,630

5,090

35

2,766

4,419

3,380

4,290

3,340

4,290

6,020

36

3,185

5,089

3,910

4,950

3,860

4,950

6,940

37

3,604

5,759

4,430

5,610

4,370

5,610

7,870

38

4,023

6,428

4,950

6,270

4,890

6,270

8,790

39

4,442

7,098

5,470

6,930

5,400

6,930

9,720

40

4,861

7,767

5,990

7,590

5,910

7,590

10,650

41

5,280

8,437

6,510

8,250

6,430

8,250

11,570

42

5,699

9,107

7,030

8,910

6,940

8,910

12,500