Bryant PURON 583B User Manual

Page 15

Advertising
background image

—15—

PERFORMANCE DATA (cont)

STANDARD INDOOR PSC MOTOR

COOLING CAPACITIES (cont)

583B048 COOLING PERFORMANCE TABLE

Temp (F)

Outdoor Air

Entering

Condenser

Evaporator Air — CFM/BF

1200 / 0.06

1600 / 0.08

2000 / 0.11

Evaporator Air — Ewb (F)

62

67

72

62

67

72

62

67

72

75

TC
SHC
kW

47.9
41.5
3.38

52.3
34.8
3.43

56.8
28.2
3.48

49.6
47.4
3.68

53.7
38.7
3.78

58.1
29.9
3.82

50.5
50.5
4.01

54.0
41.6
4.23

57.7
30.7
4.27

85

TC
SHC
kW

45.7
40.4
3.77

50.2
34.1
3.80

54.7
27.4
3.86

47.5
46.5
4.03

51.6
37.9
4.16

56.1
29.3
4.21

48.9
48.9
4.36

51.6
40.9
4.63

56.0
30.3
4.68

95

TC
SHC
kW

43.3
39.1
4.15

47.9
33.1
4.23

52.3
26.5
4.28

45.3
45.3
4.41

49.2
37.1
4.57

53.7
28.5
4.63

47.0
47.0
4.78

48.9
39.9
5.07

53.5
29.5
5.11

105

TC
SHC
kW

39.2
36.4
4.67

43.7
30.8
4.79

47.9
24.6
4.82

41.5
41.5
4.93

44.6
34.6
5.14

48.9
26.4
5.19

42.9
42.9
5.34

44.3
37.5
5.60

48.9
27.6
5.66

115

TC
SHC
kW

35.3
34.4
5.32

39.6
29.0
5.50

43.7
23.0
5.54

38.2
38.2
5.65

40.3
32.8
5.85

44.3
24.7
5.89

39.3
39.3
6.06

40.1
35.7
6.27

44.0
26.0
6.36

125

TC
SHC
kW

32.0
32.0
6.16

35.2
27.0
6.31

38.7
21.0
6.34

34.4
34.4
6.47

35.5
30.8
6.63

39.3
22.8
6.69

35.0
35.0
6.89

35.2
33.4
7.04

38.8
24.0
7.16

583B060 COOLING PERFORMANCE TABLE

Temp (F)

Outdoor Air

Entering

Condenser

Evaporator Air — CFM/BF

1500 / 0.05

1750 / 0.06

2000 / 0.07

2500 / 0.08

Evaporator Air — Ewb (F)

62

67

72

62

67

72

62

67

72

62

67

72

75

TC
SHC
kW

57.6
50.6
4.63

64.3
43.0
4.69

69.9
34.4
4.75

59.8
55.5
4.67

66.1
46.2
4.71

71.7
36.3
4.78

61.7
59.8
4.68

67.6
49.3
4.73

73.1
38.1
4.80

65.0
65.0
4.70

69.6
54.8
4.75

75.1
41.3
4.84

85

TC
SHC
kW

54.4
49.0
5.06

60.9
41.6
5.17

67.0
33.4
5.21

56.4
53.6
5.10

63.0
45.0
5.17

68.6
35.2
5.23

58.0
58.0
5.14

64.5
48.2
5.18

69.9
37.0
5.26

62.3
62.3
5.17

66.4
54.0
5.21

71.6
40.2
5.29

95

TC
SHC
kW

51.2
47.5
5.54

57.5
40.0
5.68

63.7
32.2
5.72

53.1
51.9
5.58

59.4
43.5
5.68

65.3
34.0
5.74

55.1
55.1
5.64

60.7
46.8
5.69

66.5
35.8
5.76

59.3
59.3
5.68

62.7
52.8
5.71

68.1
39.1
5.79

105

TC
SHC
kW

45.8
44.0
6.17

51.9
37.0
6.35

57.7
29.5
6.39

47.8
47.8
6.23

53.4
40.3
6.36

59.1
31.4
6.41

50.2
50.2
6.30

54.6
43.4
6.37

60.1
33.1
6.42

53.8
53.8
6.36

56.2
49.3
6.38

61.4
36.2
6.44

115

TC
SHC
kW

41.9
41.9
6.75

47.6
35.1
6.94

53.2
27.8
6.98

44.5
44.5
6.83

49.0
38.3
6.95

54.4
29.6
6.99

46.8
46.8
6.82

50.1
41.5
6.95

55.2
31.3
7.01

50.0
50.0
6.94

51.6
47.1
6.95

56.5
34.5
7.03

125

TC
SHC
kW

38.6
38.6
7.36

43.2
33.2
7.64

48.3
25.8
7.67

41.1
41.1
7.58

44.5
36.3
7.64

49.4
27.6
7.68

43.1
43.1
7.63

45.4
39.3
7.64

50.0
29.1
7.69

46.0
46.0
7.64

46.7
44.5
7.65

51.0
32.1
7.71

LEGEND

BF

Bypass Factor

Ewb

Entering Wet-Bulb

kW

Total Unit Power Input

SHC

Sensible Heat Capacity (1000 Btuh)

TC

Cooling Capacity (1000 Btuh)

PSC

Permanent Split Capacitor

NOTES:
1. Ratings are net; they account for the effects

of the evaporator-fan motor power and heat.

2. Direct interpolation is permissible. Do not extrapolate.
3. The following formulas may be used:

sensible capacity (Btuh)

t

= t

؊

ldb

edb

1.10 x cfm

t

= Wet-bulb temperature corresponding to enthalpy of air leaving

lwb

evaporator coil (h

)

lwb

total capacity (Btuh)

h

= h

؊

lwb

ewb

4.5 x cfm

Where: h

= Enthalpy of air entering evaporator coil

ewb

4. The SHC is based on 80°F edb temperature of air entering evaporator

coil. Below 80°F edb, subtract (Corr Factor x CFM) from SHC above
80°F edb, add (Corr Factor x CFM) to SHC Correction Factor = 1.10 x
(1 + BF) x (edb + 80)

Advertising