Briggs & Stratton Power Products Home Standby Generator

Installation, Start-Up and Owner’s Manual

SPECIFICATIONS

Rated Maximum Power (LP*) . . . . . . . . . . . . . . . . . .7.0 kW

Rated Maximum Load Current:

at 240 Volts . . . . . . . . . . . . . . . . . . . . . . . . . . . .29.1 Amps

at 120 Volts . . . . . . . . . . . . . . . . . . . . . . . . . . . .58.2 Amps

Rated AC Voltage . . . . . . . . . . . . . . . . . . . . . . .120/240 Volts

Rated Frequency . . . . . . . . . . . . . . . . . .60 Hz at 3600 rpm

Phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Single Phase

Power Factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.0

NG Fuel Supply Pressure . . . . . . . . . . . . . . . . . .5-7 in W.C.

LP Fuel Supply Pressure . . . . . . . . . . . . . . . . .11-14 in W.C.

Normal Operating Range -20°F (-28.8°C) to 104°F (40°C)

Output Sound Level . . .81 dB(A) at 23 ft. (7 m) at full load

Shipping Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . .280 lbs.

* Natural gas rating will depend on specific fuel but typical

derating of generator is between 10 to 20% off the LP gas
rating.

SYSTEM OPERATION

To select system operation, do the following:

1.

Push and hold START/RUN/STOP switch in START
position until LED comes on.

2.

Refer to the transfer switch manual for proper transfer
from utility to generator.

Servicing the Generator

To service generator:

1.

Remove roof by removing four screws and lifting off.

2.

Remove screw at top of control panel access door.

3.

Pull access door outward (away) from unit while
pulling door upward and out of base. Door will come
free of generator enclosure.

4.

Pull service disconnect from disconnect box.

5.

Set generator’s main circuit breaker to OFF position.

6.

Remove 15A fuse from control panel.