Table 15 – Orifice Size and Manifold Pressure for Gas Input Rate
(Tabulated Data Based on 22,000 Btuh High--Heat/14,500 Btuh for Low--Heat per Burner, Derated 4% for Each 1000 Ft Above Sea
Level)
ALTITUDE RANGE
(FT)
AVG. GAS
HEAT VALUE
(BTUH/CU
FT)
SPECIFIC GRAVITY OF NATURAL GAS
0.58
0.60
0.62
0.64
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
U.S.A.
and
Canada
0 to 2000
900
42
3.5/1.5
42
3.6/1.6
42
3.7/1.6
41
3.5/1.5
925
42
3.3/1.4
42
3.4/1.5
42
3.5/1.5
42
3.7/1.6
950
43
3.8/1.7
42
3.3/1.4
42
3.4/1.5
42
3.5/1.5
975
43
3.6/1.6
43
3.8/1.6
42
3.2/1.4
42
3.3/1.4
1000
43
3.5/1.5
43
3.6/1.6
43
3.7/1.6
43
3.8/1.7
1025
43
3.3/1.4
43
3.4/1.5
43
3.5/1.5
43
3.6/1.6
1050
44
3.6/1.6
43
3.2/1.4
43
3.4/1.5
43
3.5/1.5
1075
44
3.4/1.5
44
3.5/1.5
43
3.2/1.4
43
3.3/1.4
1100
44
3.3/1.4
44
3.4/1.5
44
3.5/1.5
43
3.2/1.4
ALTITUDE RANGE
(FT)
AVG. GAS
HEAT VALUE
(BTUH/CU
FT)
SPECIFIC GRAVITY OF NATURAL GAS
0.58
0.60
0.62
0.64
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
U.S.A.
and
Canada
U.S.A.
Altitudes
2001 to
3000 or
Canada
Altitudes
2001 to
4500
800
42
3.4/1.5
42
3.5/1.5
42
3.6/1.6
42
3.7/1.6
825
42
3.2/1.4
42
3.3/1.4
42
3.4/1.5
42
3.5/1.5
850
43
3.7/1.6
43
3.8/1.6
42
3.2/1.4
42
3.3/1.4
875
43
3.5/1.5
43
3.6/1.6
43
3.7/1.6
43
3.8/1.7
900
43
3.3/1.4
43
3.4/1.5
43
3.5/1.5
43
3.6/1.6
925
44
3.5/1.5
43
3.2/1.4
43
3.3/1.4
43
3.4/1.5
950
44
3.4/1.5
44
3.5/1.5
44
3.6/1.6
43
3.2/1.4
975
44
3.2/1.4
44
3.3/1.4
44
3.4/1.5
44
3.5/1.5
1000
45
3.7/1.6
45
3.8/1.7
44
3.2/1.4
44
3.4/1.5
ALTITUDE RANGE
(FT)
AVG. GAS
HEAT VALUE
(BTUH/CU
FT)
SPECIFIC GRAVITY OF NATURAL GAS
0.58
0.60
0.62
0.64
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
U.S.A.
Only
3001 to
4000
775
42
3.2/1.4
42
3.3/1.4
42
3.4/1.5
42
3.5/1.5
800
43
3.6/1.6
43
3.8/1.6
42
3.2/1.4
42
3.3/1.4
825
43
3.4/1.5
43
3.5/1.5
43
3.7/1.6
43
3.8/1.6
850
43
3.2/1.4
43
3.3/1.4
43
3.4/1.5
43
3.6/1.5
875
44
3.5/1.5
44
3.6/1.6
43
3.3/1.4
43
3.4/1.5
900
44
3.3/1.4
44
3.4/1.5
44
3.5/1.5
43
3.2/1.4
925
45
3.8/1.6
44
3.2/1.4
44
3.3/1.5
44
3.4/1.5
950
46
3.8/1.6
45
3.7/1.6
45
3.8/1.7
44
3.3/1.4
ALTITUDE RANGE
(FT)
AVG. GAS
HEAT VALUE
(BTUH/CU
FT)
SPECIFIC GRAVITY OF NATURAL GAS
0.58
0.60
0.62
0.64
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
U.S.A.
Only
4001 to
5000
750
43
3.6/1.6
43
3.8/1.6
42
3.2/1.4
42
3.3/1.4
775
43
3.4/1.5
43
3.5/1.5
43
3.6/1.6
43
3.8/1.6
800
43
3.2/1.4
43
3.3/1.4
43
3.4/1.5
43
3.5/1.5
825
44
3.4/1.5
44
3.6/1.5
43
3.2/1.4
43
3.3/1.4
850
44
3.2/1.4
44
3.4/1.5
44
3.5/1.5
44
3.6/1.6
875
45
3.7/1.6
45
3.8/1.7
44
3.3/1.4
44
3.4/1.5
900
46
3.7/1.6
46
3.8/1.7
45
3.7/1.6
44
3.2/1.4
925
46
3.5/1.5
46
3.6/1.6
46
3.7/1.6
46
3.8/1.7
ALTITUDE RANGE
(FT)
AVG. GAS
HEAT VALUE
AT ALTITUDE
(BTUH/CU
FT)
SPECIFIC GRAVITY OF NATURAL GAS
0.58
0.60
0.62
0.64
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
U.S.A.
Only
5001 to
6000
725
43
3.4/1.5
43
3.5/1.5
43
3.6/1.6
43
3.7/1.6
750
43
3.2/1.4
43
3.3/1.4
43
3.4/1.5
43
3.5/1.5
775
44
3.4/1.5
44
3.5/1.5
43
3.2/1.4
43
3.3/1.4
800
44
3.2/1.4
44
3.3/1.4
44
3.4/1.5
44
3.5/1.5
825
46
3.8/1.7
45
3.8/1.6
44
3.2/1.4
44
3.3/1.4
850
46
3.6/1.6
46
3.7/1.6
46
3.8/1.7
45
3.8/1.6
875
47
3.8/1.7
46
3.5/1.5
46
3.6/1.6
46
3.7/1.6
900
47
3.6/1.6
47
3.8/1.6
46
3.4/1.5
46
3.5/1.5
* Orifice numbers 43 are factory installed