Troubleshooting guide, Start, Warning – Bryant 333BAV User Manual

Page 9

Advertising
background image

A96062

If inducer and burners continue to operate, check for 24v at the
gas valve. If 24v are present, verify that the thermostat is open
across R and W. If no voltage is present, turn the gas valve
control knob to the OFF position. Replace gas valve.

Is indoor blower on ?

24v should be present across C and W. If not, check for:
1. Open thermostat.
2. Open 24-v fuse (FU1) – Code 24.
3. Failed transformer.

If Code 23 is displayed, the pressure switch(es) is stuck closed.
Replace switch and/or check pressure tube for blockage.

System malfunction – Code 21.

115v should be present at the inducer motor. If so, replace inducer
motor. If not, check 115-v wiring.

Is Code 31 (high-gas-heat only), 32, 33, or 34 displayed? Check
code information label to diagnose.

Check polarity of 115-v power at J-box and control – Rapid
flashing LED
.

Check ground continuity from J-box to control.

Check flame sensor microamps (4.0 nominal; 0.5 minimum for
control to recognize flame).

24v should be present across R and C. If not, check for:
1. Open limit switch (LS) – Code 13 or 33.
2. Open flame rollout switch (FRS) – Code 13 or 33.

24v should not be present across R and G. If so, turn thermostat
FAN switch to AUTO.

If not, check for:
1. Satisfied thermostat.
2. Open inlet gas pressure switch (when used).
3. Open pressure switch (LPS) – Code 32.
4. Open draft safeguard switch (DSS) – Code 32.
5. Open auxiliary limit (ALS)(downflow only) – Code 32.
6. Open 24-v fuse (FU1) – Code 24.
7. Open limit switch (LS) – Code 13 or 33.
8. Open flame rollout switch (FRS) – Code 13 or 33.
9. Check 115-v line voltage – LED off.

Check for sources of electrical noise interference (electronic air
cleaners, nearby TV, or radio antennas).

If Code 32 is displayed check for:
1. Open gas inlet pressure switch (when used).
2. Open pressure switch (LPS) and/or tube – Code 32.
3. Open draft safeguard switch (DSS) – Code 32.
4. Open auxiliary switch (ALS)(downflow only) – Code 32.
5. Check all low-voltage wiring connections.

115v should be present at the ignitor. If so, replace the ignitor; if not,
check 115-vac wiring to ignitor.

LPS, DSS, or ALS open while HPS is closed (high-gas-heat only) –
Code 43.

Is the gas valve control knob in the OPEN or ON position?

24v should be present across the gas valve terminals C and M/P
(and C and HI for high-stage test) during the 7 sec ignition trial. If
not, check all low-voltage wiring connections to valve.

If 24v are present, and main gas does not flow:
1. Is supply pressure between 4.5- and 13.6-in. wc? If not,
adjust supply pressure.
2. If supply pressure is between 4.5- and 13.6-in. wc, replace
gas valve.

Check ignitor position.

Check burner carryover gap.

Check manifold pressure (1.3- to 1.7-in. wc for low-stage gas
heat; 3.2- to 3.8-in. wc for high-stage gas heat).

Check for proper orifice size.

Control will attempt to light burners 4 times (approximately 1 minute
between attempts – Code 34). Voltage is present at the gas valve for 7
sec during each ignition trial. System will lockout after 4 attempts.

See 2-Stage Gas-Fired Induced-Combustion Furnaces
Troubleshooting Guide (PSC and ICM Blower Motors).

Cycle 115-v power

off for 3 sec, then on.

Continuous LED?

Draft inducer motor starts.

Is Code 22 displayed?

15-sec inducer pre-purge.

Set thermostat to call for heat.

Set FAN to AUTO.

Turn thermostat OFF.

On furnace control, note current

settings for setup switches 1 (SW-1)
and 2 (SW-2) then set SW-1 to OFF

and SW-2 to ON.

If LED is flashing rapidly, check line voltage polarity.

If Code 24 is displayed, check for blown fuse.

If LED is OFF, check line voltage and 24-v transformer.

If Code 45 is displayed, replace control.

TROUBLESHOOTING

GUIDE

NOTES:

WARNING

ELECTRICAL SHOCK HAZARD

ONLY QUALIFIED AND TRAINED
SERVICE PERSONNEL SHOULD

PERFORM THIS PROCEDURE

!

Flame present when not normal.

Replace gas valve.

Ignitor warms up and glows

orange/yellow; 17-sec warm-up.

START

Yes

No

Yes

Main burners ignite.

Yes

No

Yes

Main burners stay on.

Turn thermostat to OFF; gas valve

shuts off burners; 5-sec inducer

post purge.

Indoor blower motor stops after

90, 135, 180, or 225 sec.

Yes

Yes

Furnace runs until call for

heat ends.

Yes

No

No

No

No

No

No

No

Indoor blower motor starts on

heating speed after 45-sec

warm-up period.

No

Yes

Yes

Yes

Yes

Yes

No

Replace control only if all checks

are OK.

No

Replace control only if Code 45 is

displayed, or if all checks are OK.

No

No

Replace control if Code 45 is dis-

played, or if all checks are OK.

Clean flame sensor if microamps

are below nominal.

No

Replace control only if Code 45 is

displayed, or if all checks are OK.

No

Replace control only if Code 45 is

displayed, or if all checks are OK.

No

Replace control only if Code 45 is

displayed, or if all checks are OK.

No

Refer to information label on blower compartment door
for procedure for use of LED status codes and problem
solving suggestions.
LED indicator is viewed through window in blower
compartment door.
If 115-vac power is de-energized or interrupted during
a call for heat, the indoor blower will run for 90 sec
before a gas heating cycle begins – Code 12.
After replacing any component, verify correct operating
sequence.

1.

2.

3.

4.

Heating sequence of operation

complete. Remove blower door,

move setup switch 1 (SW-1) to ON

position and repeat process to check

high-stage gas heat operation.

(When finished return SW-1 and

SW-2 to original desired settings.)

No

24v should be present across R
and C. If not, check for:

Open flame rollout switch
(FRS) – Code 33.
Open limit switch (LS) –
Code 33.
Check all low-voltage wiring
connections.

1.

2.

3.

Replace control only if Code 45 is

displayed, or if all checks are OK.

—9—

Advertising