WARNING:

The ability to properly perform mainte-

nance on this equipment requires certain expertise, me-
chanical skills, tools, and equipment. If you do not
possess these, do not attempt to perform any maintenance
on this equipment other than those procedures recom-
mended in the User’s Manual. FAILURE TO HEED
THIS WARNING COULD RESULT IN SERIOUS IN-
JURY AND POSSIBLE DAMAGE TO THIS EQUIP-
MENT.

WARNING:

Failure to follow these warnings could

result in serious injury:
1. First, turn off gas supply to the unit. Then turn off

electrical power to the unit and install lockout tag
before performing any maintenance or service on the
unit.

2. Use extreme caution when removing panels and parts.

As with any mechanical equipment, personal injury
can result from sharp edges, etc.

3. Never place anything combustible either on, or in

contact with, the unit.

4. Should overheating occur or the gas supply fail to shut

off, turn off external main manual gas valve to the unit.
Then shut off electrical supply and install lockout tag.

TABLE 13—DRY COIL AIR DELIVERY* – HORIZONTAL AND DOWNFLOW DISCHARGE –

UNIT 583A024-060 (DEDUCT 10 PERCENT FOR 208 VOLTS)

230 AND 460 VOLT

Unit

Motor

Speed

External Static Pressure (in. wg)

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

024

Low

Watts

281

282

281

278

276

—

—

—

—

—

—

Cfm

899

828

757

691

619

—

—

—

—

—

—

Med

Watts

—

—

—

375

370

363

357

352

—

—

—

Cfm

—

—

—

969

897

824

744

649

—

—

—

High

Watts

—

—

—

—

—

468

457

444

431

423

—

Cfm

—

—

—

—

—

994

913

826

730

620

—

030

Low

Watts

246

244

243

241

—

—

—

—

—

—

—

Cfm

982

860

808

736

—

—

—

—

—

—

—

Med

Watts

343

339

336

332

328

322

317

—

—

—

—

Cfm

1233

1170

1109

1038

953

855

754

—

—

—

—

High

Watts

—

—

—

—

441

432

421

410

400

—

—

Cfm

—

—

—

—

1202

1111

1021

929

826

—

—

036

Low

Watts

—

470

458

445

430

415

399

384

—

—

—

Cfm

—

1463

1406

1344

1273

1188

1091

983

—

—

—

Med

Watts

—

—

514

501

487

471

455

438

422

—

—

Cfm

—

—

1497

1428

1348

1255

1152

1042

929

—

—

High

Watts

—

—

—

646

636

626

614

602

589

—

—

Cfm

—

—

—

1491

1412

1325

1228

1120

1003

—

—

042

Low

Watts

643

625

614

605

593

574

549

518

485

454

—

Cfm

1626

1614

1579

1532

1478

1421

1361

1295

1218

1120

—

Med

Watts

—

—

—

—

726

695

661

625

591

561

540

Cfm

—

—

—

—

1731

1672

1610

1541

1456

1345

1193

High

Watts

—

—

—

—

—

—

—

790

766

742

713

Cfm

—

—

—

—

—

—

—

1699

1602

1494

1367

048

Low

Watts

614

588

577

572

566

556

539

517

491

—

—

Cfm

1591

1549

1518

1490

1460

1421

1372

1312

1242

—

—

Med

Watts

778

756

738

719

699

676

650

623

596

572

555

Cfm

1854

1837

1804

1759

1705

1643

1577

1508

1440

1375

1315

High

Watts

—

—

—

—

896

862

829

800

775

752

728

Cfm

—

—

—

—

1956

1879

1797

1709

1615

1514

1406

060

Low

Watts

834

813

782

746

712

680

652

626

—

—

—

Cfm

2016

1955

1898

1840

1781

1717

1646

1566

—

—

—

Med

Watts

941

889

851

822

797

772

745

714

679

639

—

Cfm

2379

2233

2124

2038

1964

1892

1814

1727

1626

1511

—

High

Watts

—

—

960

949

920

883

845

812

783

753

—

Cfm

—

—

2497

2224

2075

1986

1915

1831

1721

1588

—

* Air delivery values are without air filter and are for dry coil (See Table 15–583A Wet Coil Pressure Drop table).

NOTE: Deduct field-supplied air filter pressure drop and wet coil pressure drop to obtain external static pressure available for ducting.

—23—