Bryant 352MAV User Manual

Page 10

Advertising
background image

1. The inducer will start and run on high speed.

2. After 7 sec the inducer motor will continue to run while the

hot surface ignitor HSI is energized for 15 sec, then
de-energized.

3. The inducer motor changes to low speed and continues to

run the remainder of the component self-test.

4. The blower motor operates on LO GAS-HEAT speed for 7

sec.

5. The blower motor operates on HI GAS-HEAT speed for 7

sec.

6. The blower motor operates on HI COOL speed for 7 sec.

7. The gas valve and humidifier terminal HUM are not

energized for safety reasons.

A99118

Fig. 13—Inducer Housing Drain Tube

A99119

Fig. 14—Funnel in Drain and Antifreeze

Running Through Trap

—10—