Table 1B — Physical Data — 569J*07-14A/B Units — 60 Hz SI

UNIT SIZE 569J

*07A/B

*08A/B

*12A/B

*14A/B

NOMINAL CAPACITY (kW)

21.1

26.4

35.1

44

OPERATING WEIGHTS (lb)

NOVATION™ Coil (Al Tube)

149

160

190

196

Round Tube/Plate Fin Coil (Cu/Al)

176

177

222

271

REFRIGERANT TYPE

‡

R-410A

NOVATION Operating Charge, Typical (kg)

†

3.8

4.6

6.3

8.2

NOVATION Shipping Charge (kg)

2.0

2.2

2.9

3.3

RTPF Operating Charge, Typical (kg)

†

6.4

7.7

9.1

20.9

RTPF Shipping Charge (kg)

5.0

5.9

7.3

15.9

COMPRESSOR

Qty...Type

1...Scroll

1...Scroll

1...Scroll

1...Scroll

Oil Charge (oz)

1.7

1.8

3.3

3.3

CONDENSER FANS

Qty...r/s

2...18

Motor Hp NEMA

1

/

4

Diameter (mm)

560

Nominal Airflow (L/s)

2832

Watts (Total)

610

RTPF CONDENSER COIL

Material (Tube/Fin)

Cu / Al

Coil Type

3

/

8

---in RTPF

Rows/Fins per Meter (Fins/m)

2 / 670

3 / 670

Face Area (sq m total)

1.6

1.9

2.3

3.0

NOVATION CONDENSER COIL

Material (Tube/Fin)

Al / Al

Coil Type

Novation

Rows/Fins per Meter (Fins/m)

1 / 670

Face Area (sq m total)

1.6

1.6

2.3

3.0

CONTROLS

Pressurestat Settings (kPa)

High Cutout

4347 ± 70

Cut-in

3482 ± 138

Low Cutout

372 ± 21

Cut-in

807± 34

PIPING CONNECTIONS (in. ODS)

Qty...Suction

1...1

1

/

8

1...1

1

/

8

1...1

3

/

8

1...1

3

/

8

Qty...Liquid

1...

3

/

8

1...

1

/

2

1...

1

/

2

1...

5

/

8

LEGEND

RTPF — Round Tube/Plate Fin

NEMA — National Electrical Manufacturers Association

ODS — Outside Diameter Sweat (socket)

‡

Unit is factory-supplied with partial charge only.

†

Typical operating charge with 25 ft of interconnecting piping.

569J