Warning, Installation, Not good good – Advanced Protection SPDee User Manual

Page 2: Figure 3, Figure 2

Advertising
background image

2

LEADS SHOrT & STrAIGHT

X

NOT

GOOD

GOOD

Cut off

Excess Length
Do Not Loop

or Coil

Short

& Straight

Figure 2

A

B

C

G

N

BREAKER

(Type 1 or individual equipment installations may vary)

▪

Use closest

breaker to SPD

▪

Locate SPD close

to intended breaker

▪

Keep Leads Short

as Possible

▪

Avoid Sharp Bends

▪

Rotate SPD

ee

such

that LED indicator

is most visible

▪

Outdoor installation requires appropriate weather

sealing at nipple (gasket, sealing conduit, etc.)

To Protected Loads

Figure 1

Sealing gasket:

two choices

1.) At 3/4" nom.

thread: ID is 1.05"

2.) At 0.14" high 'base

step': ID is 1.25"

Figure 3

INSTALLATION

Pre-Plan your installation. You need to accomplish the following:

▪

Meet all National and Local codes (NEC

®

Article 285 and UL 1449 address SPDs).

▪

Confirm System voltage to SPD voltage (120V SPD will fail instantly on 240V, 277V, etc.).

▪

Mount SPD as close to panel or equipment as possible to keep leads short.

(long leads hurt performance substantially).

▪

Ensure leads are as short and straight as possible, including neutral and ground. If using a

breaker, use a breaker position that is close to the SPD and the panel’s neutral & ground.

▪

If using a breaker, recommended breaker size is 30A due to 10 AWG conductor.

▪

Make sure system is grounded per NEC

®

and clear of faults before energizing SPD.

(inadvertent system problem may fail SPD).

▪

Never Hi-Pot test Any SPD. (will prematurely fail SPD).

1. Use voltmeter to check voltages and ensure correct SPD. See Data Sheet for specs and wire-outs.

2. Determine Mounting method (See Figure 5) – weather resistant equipment may be required.

3. If SPD has optional Dry Contact, pre-plan its installation.

4. Remove power from panel/source. Confirm panel/source is deenergized.

5. Identify breaker location and SPD location. Position SPD such that LED is best visible.

6. Mount SPD – weather resistant applications require additional sealing, o-rings, etc. (not included)

- Remove an appropriately sized knockout from panel.

- Connect conductors as appropriate – short and straight as possible (Hi-Legs are Phase B).

7. Label or mark conductors as appropriate (neutral: white, ground: green, energized: black, hi-leg: orange).

8. Make sure system is bonded per NEC

®

and is clear of hazards or faults before energizing.

(N-G bonding not per NEC

®

will fail SPDs: #1 cause of SPD failures)

9. Energize and confirm proper operation of green LED indicator and/or options.

(Affix supplemental label accessory if appropriate. See Figure 5.)

V

WARNING

▪

Confirm XO N-G Bonding at Upstream Transformer

▪

Do Not Hi-Pot Test

▪

Resulting Damage is not Covered Under Warranty

VERIFY THAT ALL POWER CIRCUITS ARE

DEENERGIZED BEFORE MAKING CONNECTIONS

All electrical connections should be performed by a qualified

(licensed) electrician or technician. All wiring must comply with

the National Electrical Code (NEC

®

) and applicable local codes.

TYPICAL PANEL

INSTALLATION

V

WARNING

Advertising