Chapter 4 - i/o interfacing – B&B Electronics RS-232 Digital I/O Module 232SDD16 User Manual

Page 11

Advertising
background image

232SDD16-1005 Manual

17

B&B Electronics -- PO Box 1040 -- Ottawa, IL 61350

PH (815) 433-5100 -- FAX (815) 433-5104

Chapter 4 - I/O Interfacing


This chapter will explain "HIGH" and "LOW" states and show

some general examples of how to interface to the I/O lines. Caution
must be taken not to exceed 232SDD16 specifications listed in
Chapter 1 when interfacing to external devices. Failure to stay
within these specifications could result in damage to the unit and will
void warranty.


Digital Inputs


As stated earlier, digital input lines are CMOS/TTL compatible

and can only handle voltages from 0Vdc to +5Vdc.

Digital inputs are used to sense a HIGH or a LOW state. This

can be accomplished via switch closures, contact closures, or a
solid state digital signal. When an I/O line, defined as an input,
senses a voltage level above +2.0Vdc it will be considered "HIGH"
and its input state will be read as a "1". Conversely, when an input
senses a voltage level below +1.0Vdc it will be considered "LOW"
and its input state will be read as a "0".

Inputs can also be used to sense AC voltages by using

mechanical or solid state relays. Solid state relays are available
from many manufacturers.

Figures 4.1 - 4.4 show examples of some typical input interfaces.

Figure 4.1 - Switch Input

18 232SDD16-1005

Manual

B&B Electronics -- PO Box 1040 -- Ottawa, IL 61350

PH (815) 433-5100 -- FAX (815) 433-5104

Figure 4.2 - Solid State Input

Figure 4.3 - Isolated Mechanical Input

Advertising