Bryant ASPAS1BBA015 User Manual

Page 118

Advertising
background image

Page 118

SECTION 4.4

DIAGNOSTIC TESTS

6. Connect one meter test lead to Wire 351 (previously

removed from SW2). Connect the other meter test lead
to Pin Location J3 (Wire 351). CONTINUITY should be
measured.

7. Connect one meter test lead to Wire 351 (previously

removed from SW2). Connect the other meter test lead
to the ground terminal. INFINITY should be measured.

8. Connect one meter test lead to Wire 0 (previously

removed from SW2). Connect the other meter test lead to
the ground terminal. CONTINUITY should be measured.

RESULTS:

1. If the Set Exercise Switch (SW2) fails Step 3 or Step 4,

replace the switch.

2. If CONTINUITY was NOT measured in Step 6, OR if it

WAS measured in Step 7, repair or replace Wire 351
between SW2 and Connector J2.

3. If CONTINUITY was NOT measured in Step 8, repair or

replace Wire 0 between SW2 and the ground terminal.

TEST 74 - CHECK REMOTE START WIRING

(IF EQUIPPED)

DISCUSSION:
On some earlier models a remote start connection
was available. If these two wires are connected
together while the generator is in “AUTO,” the
generator will start.

PROCEDURE:

1. Set the Auto-Off-Manual switch to OFF.

2. Set a VOM to measure resistance.

3. Disconnect the 17-pin connector (J1) from the circuit

board.

4. If the remote star t connections have been used,

disconnect the customer wires from the terminal
connector at Wire 178 and Wire 183.

5. Connect one meter test lead to Wire 178 at the terminal

connector. Connect the other meter test lead to Wire
183 at the terminal connector. INFINITY should be
measured.

6. If the remote start connections have been used, connect

the meter test leads across customer supplied wiring. If
CONTINUITY is measured, customer supplied circuit is
causing startup.

RESULTS:

1. If CONTINUITY was measured in Step 5, a short exists

between Wire 178 and Wire 183. Repair or replace Wire
178 and/or Wire 183 between terminal connector and
SW1.

TEST 75 - CHECK BATTERY VOLTAGE

CIRCUIT

DISCUSSION:
If the 15 amp fuse blows immediately after
replacement, Wire 15 should be checked for a fault.

PROCEDURE:

1. Set the Auto-Off-Manual switch to OFF.

2. Disconnect the 17-pin connector (J1) from the circuit

board.

3. Set a VOM to measure resistance.

4. Disconnect Wire 15 from the fuse holder (F1).

5. Connect one meter test lead to Wire 15 (removed from

fuse holder in previous step). Connect the other meter
test lead to the ground terminal. INFINITY should be
measured.

RESULTS:

1. If CONTINUITY was measured in Step 5, repair or

replace Wire 15 between the fuse holder (F1) and SW1,
or between SW1 and Connector J1.

2. If INFINITY was measured in Step 5, replace the circuit

board and retest.

TEST 76 - CHECK CRANKING AND RUNNING

CIRCUITS

DISCUSSION:
This test will check all of the circuits that are “HOT”
with battery voltage and which could cause the F1
Fuse to blow.

PROCEDURE:

1. Set a VOM to measure resistance.

2. Disconnect the 17-pin connector (J1) from the circuit

board.

3. Connect one meter test lead to the ground terminal.

Connect the other meter test lead to each of the
following J1 Connector pin locations:

PART 4

DC CONTROL