If the heater is to be shut down for cleaning, maintenance or

repair, follow steps 1 - 5. Otherwise, simply turn thermostat

to off or no heat for standard shut down.

1. Close all manual fuel supply valves.

2. With the heater lit, allow heater to burn off excess fuel

in gas supply hose.

3. Turn the knob (if applicable) on the gas control to off.

4. Turn thermostat to off or no heat position.

5. Disconnect the heater from the electrical supply.

11

Start-Up Instructions

Shut-Down Instructions

GAS SHUT OFF KNOB

PILOT BUTTON

PILOT

OFF

ON

Follow steps 1 - 8 on initial start-up after heater installation

by a qualified gas heater service person. For normal start-

up, simply turn thermostat above room temperature. The

heater will start.

1. Open all manual fuel supply valves and check for gas

leaks using approved certified leak detectors.

2. The gas control valve incorporates a manual gas shut

off feature. Position the indicator on the shut off knob

to pilot.

3. Fully depress the red pilot button located on the

control valve while applying flame to the pilot light.

4. Keep the button depressed for about 30 seconds to

allow the thermocouple to warm up so the pilot stays

lit after you release the pilot button. On new

installations it may take about a minute for the gas to

purge out any air in the pilot line before the pilot lights.

5. Position the knob to on.

FIG. 6

6. Connect the heater’s electrical cord to an approved

electrical outlet.

7.

Set thermostat to a point above room temperature.

the heater will light. Reset thermostat to desired room

temperature.

8. Do not exceed input rating stamped on nameplate of

appliance, or manufacturer’s recommended burner

orifice pressure for size orifice(s) used.