Heater specifications, Model – L.B. White 220 Therma Grow User Manual

Page 5

Advertising
background image

4

4

Heater Specifications

SPECIFICATIONS

HW220

Propane

Natural

Gas

Gas

Maximum Input (BTUH)

220,000

EXHAUST FAN

550 CFM

SHUTTERED AIR INLET

220 sq. in.

100 sq. in.

MAX.

13.5

11.0

MIN.

11.0

7.0

5.0

3.1

10.19 lbs.

220 cu. ft.

Ball Bearing

1/2 H.P.

1,100 RPM

115/60/1

230/60/1

17.1

6.7

6.2

2.6

35 x 25 x 30

TOP

1 ft.

SIDES

1 ft.

BACK

1 ft.

BLOWER
OUTLET

GAS

Propane Gas Supply — 6 ft. (1.83 m)

SUPPLY

Natural Gas Supply — N/A

(1) Air inlets and exhaust outlets must be electromechanically operated and electrically interlocked with the

heater to prevent heater operation if air inlet and exhaust outlet do not open when heating is required.

Model

Indoor Mounting Air
Exchange Requirements

(1)

Burner Manifold
Pressure (In. W.C.)

Electrical Supply
(Volts/Hz/Phase)

Amp Draw

Dimensions (inches)
L x W x H

Minimum Safe
Distances From Nearest
Combustible Materials

STARTING

CONTINUOUS
OPERATION

Motor Characteristics

Fuel Consumption Per
Hour

Inlet Gas Supply
Pressure Acceptable at
the Inlet of the Heater
for Purpose of Input
Adjustment (In. W.C.)

6 ft. (1.83 m)

Outdoor Mounting Air
Exchange Requirements

(1)

SHUTTERED
EXHAUST OUTLET

115 VOLT MOTOR

230 VOLT MOTOR

115 VOLT MOTOR

230 VOLT MOTOR