R-410A—QUICK REFERENCE GUIDE

•

R-410A refrigerant operates at 50-70 percent higher pressures than R-22. Be sure that servicing equipment and replacement
components are designed to operate with R-410A.

•

R-410A refrigerant cylinders are rose colored.

•

R-410A refrigerant cylinders have a dip tube which allows liquid to flow out of cylinder in upright position.

•

Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.

•

R-410A systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose.

•

Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low-side retard.

•

Use hoses with 700 psig service pressure rating.

•

Leak detectors should be designed to detect HFC refrigerant.

•

R-410A, as with other HFCs, is only compatible with POE oils.

•

Vacuum pumps will not remove moisture from oil.

•

Do not use liquid-line filter driers with rated working pressures less than 600 psig.

•

Do not install a suction-line filter drier in liquid line.

•

POE oils absorb moisture rapidly. Do not expose oil to atmosphere.

•

POE oils may cause damage to certain plastics and roofing materials.

•

Wrap all filter driers and service valves with wet cloth when brazing.

•

A liquid-line filter drier is required on every unit.

•

Do not use an R-22 TXV.

•

If indoor unit is equipped with an R-22 TXV, it must be changed to an R-410A TXV.

•

Never open system to atmosphere while it is under a vacuum.

•

When system must be opened for service, break vacuum with dry nitrogen prior to opening to atmosphere.

•

Always replace filter drier after opening system for service.

•

Do not vent R-410A into the atmosphere.

•

Do not use capillary tube coils.

•

Observe all warnings, cautions, and bold text.