NOTE:

The core should only be serviced when outdoor

temperature is 60°F to 75°F (16°C to 24°C) and it is dry.

UNIT COMPONENT DAMAGE HAZARD
Failure to follow this caution may result in equipment

damage or improper operation.
DO NOT use water to clean core or damage will result. In

addition, before servicing or removing the core inspect the

edges to see if they appear soft (or slightly expanded). This

can be normal and due to moisture in the air. DO NOT

handle or service core until it is dry or air passages can

become damaged and/or closed.

CAUTION

!

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury

or death.
Before installing or servicing system, always turn off main

power to system. There may be more than 1 disconnect

switch.

!

WARNING

CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care

and wear appropriate protective clothing and gloves when

handling parts.

CAUTION

!

TROUBLESHOOTING

NOTE: Reference Table 5 Troubleshooting Chart
This can be a quick guide in resolving unit problems. It is also

recommended to review and understand Wall Control Board
Operation and Care and Maintenance sections before continuing.
NOTE: If there is a short circuit or an open circuit at thermistor,
CPU will go into a 5 minute defrost cycle every 20 minutes. This
feature is not there on older board versions with 3 pin jumpers.

Override Test

To use override test function, a thermistor must be connected to the

control board. Unit must not be in defrost mode during an override
test.
High Speed

1. Disconnect ERV/HRV from 115VAC.
1. Unplug wall control wires at control module terminal block in-

side ERV/HRV.

2. Plug ERV/HRV back to 115VAC.
3. Attach a wire across J3--8 and J3--9 (B and G) on control mod-

ule terminal block.

4. Close door, this will initiate a high--speed exchange.

Low Speed

1. Unplug ERV/HRV from 115VAC.
2. Disconnect wall control wires at control module terminal block

inside ERV/HRV.

3. Plug ERV/HRV back to 115VAC.
4. Connect a 3.0 K ohm resistor between B and G on control

module terminal block.

5. Close door, this will initiate a low--speed exchange.

Blower Speed Selection
Three--speed blowers are factory connected to electronic control
board on HIGH-- and LOW--speed taps of blowers. Installer can

easily change low--speed tap to medium--speed tap so electronic
control will select between high and medium speed. Connections

can be changed at motor location.
To change low speed to medium speed, proceed as follows:

1. Unplug unit from 115VAC.
2. Locate blower assembly.
3. Locate red wire an blue wire coming from blower assembly.
4. Unplug red wire from quick connect.
5. Unplug protecting cap quick connection from blue wire and

put on red wire coming from blower. The cap is a safety insula-

tor.

6. Connect red wire of main harness to blue wire.
7. Replace wires.