Pv trim, Hart troubleshooting, Hart master does not connect to sonartrac – CiDRA SONARtrac Quick Start User Manual

Page 25: The hart activity icon does not appear on display, The hart activity icon does appear on display, Connection to sonartrac is intermittent, Hart troubleshooting -5, Hart master does not connect to sonartrac -5, Connection to sonartrac is intermittent -5

Advertising
background image

4.2.6.9 PV

Trim

Value subtracted from the HART ‘Primary Variable’ (i.e. VF).

4.3 HART

Troubleshooting

4.3.1

HART Master Does Not Connect to SONARtrac

4.3.1.1

The HART Activity Icon Does NOT Appear on Display

Check the Internal/External POWER SEL setting for 4-20mA CH 1.

Check that the Universal Command Rev matches the master.

Check the polling address – 0 if Point to Point, unique if multi-drop.

4.3.1.2

The HART Activity Icon DOES Appear on Display

Check that the Universal Command Rev matches the master.

Check the polling address – 0 if Point to Point, unique if multi-drop.

4.3.2

Primary Value Read Using HART Does Not Match SONARtrac

Check that the PV Trim value is 0.

4.3.3

Connection to SONARtrac Is Intermittent

Increase the PREAMBLES or RESP. PREAMBLES on SONARtrac
transmitter.

Copyright © 2007 CiDRA Corporation

Page 4-5

20984-01 Rev 01

Advertising