8.1.5.

Control Page Default Values

Menu Item

Display

Default

Range

Setting

Cycle Time

Control Cycle
Time

1

1 to 60 seconds

High limit setpoint

Control Hi-Lim
SP

Max
HiLimSP

MinHiLimSP – MaxHiLimSP

24

High limit band

Control Hi-Lim
Band

Off

Off, 3°C to 11°C (5°F to 20°F)

Power fail recovery

Control PwrFRec

Stop

Stop, Restart, Hold, Resume

Recovery time limit

Control
PwrFTime

00m00s

00m00s to 99m59s

Powerup start
enable

Control EPwrStrt

Dis

Dis, En

Powerup Start
Mode

Control StrtMode

Off

Off, Manual, Timer, Pro-1 to
Pro-8

Hysteresis

Control Hyst

3°C

1°C to 56°C (1°F to 100°F)

Process out low

Control RetOutLo 80°C

-73°C to 760°C (-100°F to
1400°F)

Process out high

Control RetOutHi

400°C

-73°C to 760°C (-100°F to
1400°F)

Time scale

Control
TimeScale

hh:mm

hh:mm or mm:ss

Key press beep

Control KeyBeep

On

On or Off

End of cycle beep

Control EOCBeep Off

On or Off

Alarm beep

Control
AlarmBeep

Off

On or Off

8.1.6. Communication (Optional) Page Default Values

Menu Item

Display

Default

Range

Setting

Address

Communication
CommAddr

1

1 to 247

Mode

Communication
CommMode

OFF

OFF, Modbus

Baud rate

Communication Baud
Rate

19.2K

2400, 4800,
9600, 19.2K,
38.4K

Parity

Communication Parity

None

None, Odd, Even