7
Figure 3: MMCP - OCP Wiring Chart
Figure 4: MMCP – Monitor Junction Box
Wiring Chart
Figure 5: #81471068 MMCP/Monitor Motors - (Optional Valve and Auxiliary Device) Wiring Diagram
WIRE SIZE FOR CONDUCTORS BETWEEN MONITOR
MOTOR CONTROL PANEL AND
OPERATOR CONTROL PANEL OR VALVES
CONDUCTOR LENGTH
WIRE SIZE
UP TO 750 FEET (228 m)
18 AWG (0.75 mm
2
)
750 TO 1500 FEET (457 m)
16 AWG (1.0 mm
2
)
1500 TO 2500 FEET (762 m)
14 AWG (2.5 mm
2
)
2500 TO 3500 FEET (1066 m)
12 AWG (4.0 mm
2
)
WIRE SIZE FOR CONDUCTORS BETWEEN
MONITOR MOTOR CONTROL PANEL AND MONITOR
JUNCTION BOX
CONDUCTOR LENGTH
WIRE SIZE
UP TO 75 FEET (22 m)
18 AWG (0.75 mm
2
)
75 TO 100 FEET (30 m)
16 AWG (1.0 mm
2
)
100 TO 200 FEET (60 m)
14 AWG (2.5 mm
2
)
200 TO 400 FEET (121 m)
12 AWG (4.0 mm
2
)