Design – ERICO ISODC Isolated Downconductor System User Manual
Page 6
Advertising

6
www.erico.com
Table 1. Height versus horizontal distance using protection angle method. (continued)
Height h of air-
termination (m)
Distance d (m) and protection angle
␣Њ (rounded down to nearest degree)
LPL I
LPL II
LPL III
LPL IV
Distance
Angle
Distance
Angle
Distance
Angle
Distance
Angle
41
19.12
25
29.79
36
42
18.70
24
30.51
36
43
18.25
23
30.11
35
44
18.68
23
28.57
33
45
18.18
22
29.22
33
46
28.74
32
47
28.24
31
48
27.71
30
49
28.29
30
50
28.87
30
51
28.27
29
52
28.82
29
53
29.38
29
54
28.71
28
55
28.02
27
56
27.31
26
57
26.58
25
58
25.82
24
59
25.04
23
60
25.47
23
h
1
d
1
d
2
h
2
␣
1
Protected
Not Protected
Table 2. Lightning Protection Levels
Lightning Protection Level
(Class of LPS)
Peak current (10/350 µs)
Probability of exceedance
I
200 kA
≤ 1 %
II
150 kA
≤ 3 %
III
100 kA
≤ 9 %
IV
100 kA
≤ 16 %
1. DESIGN
(continued)
␣
2
Advertising