E T C I n s t a l l a t i o n G u i d e

Paradigm 18" Touchscreen Wall Mount Kit

Paradigm 18" Touchscreen Wall Mount Kit Installation Guide Page 2 of 4

Electronic Theatre Controls, Inc.

Install Power and Data

The wall mounting back box includes two removable compartments; one left side which includes a
terminal strip for power input and one right side for installation of the provided RJ45 connector for data
termination.

Step 1:

Run conduit to the left side of the backbox for power (AC input terminal block is provided),

and to the right side of the backbox for data (Ethernet CAT5e).

Step 2:

Remove the left side and right side compartments from the backbox. Each side is secured
with a screw.

Step 3:

Terminate the AC power circuit wiring to the terminal block provided on the left side
compartment. The input terminal is labeled for convenience.

Step 4:

Re-install the left side compartment to the backbox and secure it in place with the screw
provided.

Step 5:

Locate the RJ45 connector (provided in the wall mounting
kit).

Step 6:

Using a standard 110 punch down tool (not provided),
terminate the incoming CAT5e data wires to the RJ45
connector. Reference the connector label for the CAT5e wire
termination color code.

Step 7:

Locate the stuffer cap (clear protective cap) on the underside of the
RJ45 connector and snap it over the wire terminations.

Step 8:

Insert the RJ45 connector to the right side compartment, pressing
the connector portion only through the provided hole until it snaps
into place.

Step 9:

Reinstall the right side compartment to the backbox, securing it in
place with the provided screws.

Purpose

Description

Power input - AC Input 100-240V, 1.5A, 50-60Hz

3 wire - line (brown), neutral (blue) and earth (green/yellow)

Ethernet (network)

CAT5e (follow IEEE802.3 and terminate to T568B standard)

N o t e :

Power and data must be run in separate conduit.

N o t e :

All Ethernet terminations must follow IEEE 802.3 and be terminated to the T568B

standard. The RJ45 connector provides insulation displacement. Do not strip the

wires.

removable

stuffer cap

RJ45

connector