Operating Instructions Safety System CES-AZ-ABS-01B
15
4. To activate the actuator code from the teach-in operation in the evaluation unit,
the operating voltage must then be switched off at the evaluation unit for min.
10 seconds.
5. Check functioning of the safety guard.
Teach-in function for a new actuator
1. Apply the operating voltage to the evaluation unit
2. Move new actuator to the read head (observe distance < S
ao
)
Ì
teach-in operation starts, green LED flashes (approx. 1 Hz)
3. Teach-in operation completed (after 60 seconds)
Ì
green LED goes out, new code saved, old code deactivated
4. To activate the new actuator code from the teach-in operation in the evaluation
unit, the operating voltage must then be switched off for min. 10 seconds.
5. Check functioning of the safety guard.