System manual safety system ces-a-c5, Safety switch ces-a-c5 – EUCHNER CES-A-C5H-01 (Unicode) User Manual
Page 13
Advertising

System Manual Safety System CES-A-C5...
13
Safety switch CES-A-C5...
Voltage drop as a function of switching current and
cable length (examples)
Switching current
Cable length "l"
Voltage drop
Max. voltage drop
Max. voltage drop
[mA]
[m]
Output [V]
Cable [V]
Total [V]
6
(safety control system with
pulsed signals)
1 -100
1,4
0,1
1,5
101 - 300
1,4
0,4
1,8
50
(safety relay)
1 - 15
1,5
0,
1,7
16 - 50
1,5
0,5
,0
51 - 100
1,5
1,0
,5
101 - 300
1,5
3,0
3,5
400
(e. g. small contactor)
1 - 15
1,7
1,
,9
16 - 50
1,7
4,0
5,7
51 - 100
1,7
8,0
9,7
101 - 300
1,7
-
-