Operating Instructions Safety Switch CET.-AR-...-CH-...
19
Requirements for connection cables
Caution!
Risk of damage to equipment or malfunctions as a result of incorrect connec-
tion cables.
Ì
Use connection components and connection cables from EUCHNER
Ì
On the usage of other connection components, the requirements in the fol-
lowing table apply. EUCHNER provides no warranty for safe function in case
of failure to comply with these requirements.
Observe the following requirements with respect to the connection cables:
For safety switch CET-AR with plug connectors 2 x M12
Parameter
Value
Unit
Wire cross-section min.
0.34
mm²
R max.
60
W/km
C max.
120
nF/km
L max.
0.65
mH/km
Recommended cable type
LIYY 8x or 5x 0.34 mm²
For safety switches CET-AR with plug connector RC18
Parameter
Value
Unit
Wire cross-section min.
0.34
mm²
R max.
60
W/km
C max.
120
nF/km
L max.
0.65
mH/km
Recommended cable type
LIFY11Y min. 19-cores