EUCHNER ESM-2H2 Series User Manual

Hand safety relay, series esm-2h2, User information

Advertising
background image

User Information

1

EUCHNER GmbH + Co. KG Kohlhammerstraße 16 D-70771 Leinfelden-Echterdingen Tel. +49/711/75 97-0 Fax +49/711/75 33 16 www.euchner.de [email protected]

2-Hand Safety Relay, Series ESM-2H2..

•

Up to PL e, SILCL 3, category 4

Correct Use

The ESM-2H2.. 2-hand safety relay is an extremely
compact, universal safety two-hand control unit. It
complies with EN574, Typ III C, and is intended for use
in safety circuits that are designed in accordance with
EN 60204-1, e.g. on presses, punches and bending
tools. Due to the internal error monitoring, the 2-hand
safety relay can be used, despite very compact dimen-
sions, for all applications up to the highest safety cate-
gory 4 and PL e according to EN ISO 13849-1, SILCL 3
according to EN 62061 or Typ III C according to EN 574.

Features

•

2 safe, redundant relay outputs

•

Cyclical monitoring of the output contacts

•

Feedback loop for monitoring downstream contactors or
expansion modules

•

Short circuit and earth fault monitoring

•

Extrem compact housing

Function

The EUCHNER 2-hand safety relay ESM-2H2.. is suitable
for setting up and monitoring two-hand circuits and is used
to protect the operators. Dangerous work steps can only be
triggered when both two-hand buttons connected are ope-
rated simultaneously, i.e. within 0.5s.

It is to be ensured a single fault or a malfunction does not
result in the loss of the safety function and every fault is
detected by the cyclic self-monitoring at the latest prior to
the next actuation.

When the operating voltage is applied to A1-A2 and the
feedback loop X1-X2 is closed, the ESM-2H2.. is ready for
use. To be able to initiate a switching operation, the output
relays must be de-energized. The output relays only switch
to the energized position when the two-hand buttons T1
and T2 are operated simultaneously, i.e. within 0.5s.

Fig. 1 Block diagram ESM-2H2..

•

It is not allowed to open the device, tamper with the devi-
ce or bypass the safety devices.

•

All relevant sefety regulations and standards are to be
observed.

•

The overall concept for the control system in which the
device is integrated is to be validated.

•

Failure to observe the safety regulations can result in
death, serious injury and serious damage.

Installation

As per DIN EN 60204-1, the device is intended for installa-
tion in control cabinets with a minimum degree of protection
of IP54. It is mounted on a 35-mm DIN rail according to
DIN EN 60715 TH35.

Safety Precauti-
ons

•

Installation an setup are only allowed to be undertaken
by trained personell.

•

The electrical connection is only allowed to be made with
the device and wiring isolated.

•

The wiring must comply with the instructions in this user
information, otherwise there is a risk that the safety
function will be lost.

•

As per EN 60204-1 the device is intended for installation
in control cabinets with a minimum degree of protection
of IP54.

Fig. 2 Installation/removal

Electrical Connec-
tion

•

When the 24V version is used, a safety transformer
according to EN 61558-2-6 or a power supply unit with
electrical isolation from the mains must be connected.

•

External fusing of the safety contacts (4A slow-blow or
6A quick-action or 10A gG) must be provided.

•

A maximum length of the control lines of 1000 meters
with a line cross section of 0.75 mm

2

must not be excee-

ded.

•

The line cross section must not exceed 2.5 mm

2

.

•

If the device does not function after commissioning, it
must be returned to the manufacturer unopened. Ope-
ning the device will void the warranty.

Fig. 3 Connections

A1:

Power supply

A2.

Power supply

S11:

Control line T1

S12:

Control line T1

S13:

Control line T1

S21:

Control line T2

S22:

Control line T2

S23:

Control line T2

X1; X2:

Feedback loop

13-14:

Safety contact 1

23-24:

Safety contact 2

(not dor plug-in terminals)

The output relays are not switched if:

•

only one two-hand button is actuated or the time between the actuation of the 2 two-hand buttons is greater than 0.5s,

•

the feedback loop is open (fault in the external contactor),

•

another error (short circuit, cable break, error in the switching device) has occurred.

When T1 and/or T2 are/is released, the output relays opens immediately. In order to trigger a new operation, both two-hand

buttons must first be released and the feedback loop must be closed.