INSTALLATION

Step 1 — Check Perfect Air Air Purifier Components

PERSONAL INJURY HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and

wear appropriate protective clothing and gloves when

handling parts.

CAUTION

!

Carefully remove all items from the box.
Step 2 — Identify Mounting Location

a. Identify a mounting orientation for the Perfect Air Air Purifier

in the return air duct (see Fig. 4).

b. Ensure airflow direction through the Perfect Air Air Purifier

matches the arrows on the face of the air purifier cartridge.
The Perfect Air Air Purifier or door can be rotated 180_ to

accommodate the cabinet orientation.

c. The location of the Perfect Air Air Purifier should be readily

accessible. Enough room should be provided for periodic re-

placement of the air purifier cartridges.

Step 3 — Mount Cabinet

a. Turn off power to the heating and cooling system.

b. Remove the existing fan coil filter and discard. Excessive sys-

tem static pressure may result if the Perfect Air Air Purifier is

used with other filtration devices.

c. Remove the air purifier cartridge and enhancement module

from the Perfect Air Air Purifier cabinet.

d. Position the cabinet between the fan coil and return air duct

(see Fig. 4 and 5). A transition duct may be required.

NOTE: The fan coil cabinet screws holding the filter rack should
be used to attach the air purifier cabinet.

a. Gasket tape between the fan coil and the air purifier cabinet is

already factory installed.

b. Mounting holes are provided for fan coil attachment.

c. Use return duct adapters provided to attach return ductwork

(See Fig. 6).

d. Seal seams with tape or caulking after the Perfect Air Air Puri-

fier cabinet has been secured.

A06517

Downflow

A06371

Horizontal

Airflow

A06374

Upflow

Airflow

Airflow

Fig. 4 -- Perfect Air Air Purifier Cabinet Orientation

Return Duct

Adapters (x4)

A06389

Mounting Cabinet Vertical

Return Duct

Adapters (x4)

A06388

Mounting Cabinet Horizontal

Fig. 5 -- Mounting Perfect Air Air Purifier Cabinet For Fan Coils

GAP