I Product Description

The FCM070, FCM090 and FCM120 are aluminum gas fi red condensing boilers designed for use in forced
hot water heating systems requiring supply water temperatures of 180°F or less. These boilers are designed for
installation on a wall, however they may be fl oor mounted using an optional pedestal kit available from U.S. Boiler
Company, Inc. This boiler may be vented vertically or horizontally with combustion air supplied from outdoors.
This boiler is not designed for use in gravity hot water systems or systems containing signifi cant amounts of
dissolved oxygen.

II Specifi cations

MODEL*

NO. OF

SECTIONS

MAXIMUM

INPUT

(BTU/hr)

MINIMUM

INPUT

(BTU/hr)

D.O.E.

HEATING

CAPACITY

(BTU/hr)

IBR NET

RATING

(BTU/hr)

AFUE (%)

WATER

VOLUME

(Gal.)

APPROX.

NET

WEIGHT

(lb)

FCM070

mono block

70,000

30,000

63,000

55,000

95.4

0.41

102

FCM090

mono block

90,000

30,000

80,000

70,000

94.5

0.41

102

FCM120

mono block

120,000

40,000

107,000

93,000

95.2

0.62

110

* Add suffi x “N” for natural gas and “P” for propane. Ratings are the same for both fuels.

Using 60/100mm Concentric Vent System Supplied with the Boiler................................................................25 in.
Using Optional 60/100mm Concentric Vent Components:

FCM070 ...................................................................................... 32 ft
FCM090 ...................................................................................... 32 ft
FCM120 ...................................................................................... 18 ft

Using Approved 3” AL29-4C Horizontal Stainless Vent System and Optional Stainless Steel Vent Kit..........55 ft

See Vent Section for additional venting options and requirements

TABLE 2.3: MAXIMUM VENT LENGTHS