NOTE: The CF switches are factory set to provide continuous fan airflow equal to low-heat mode.
5. Replace main furnace door and blower access panel.
C. Setup Switches (SW)
The control center has 8 setup switches that may be set to meet the application requirements. Position these setup switches for the appropriate
requirement.
1. Remove main furnace door and blower access panel.
Table 9—Air Conditioning (A/C) Airflow Switch Position
AIR
CONDITIONER
(TONS)
CFM AIRFLOW
A/C SETUP
SWITCH POSITION
ALLOWABLE FURNACE MODEL SETUP
A/C-1
A/C-2
A/C-3
042040
042060
042080
060080
060100
060120
Default
1200 or
2000
OFF
OFF
OFF
3 Tons
1200 CFM
3 Tons
2000 CFM
3 Tons
1200 CFM
5 Tons
2000 CFM
5 Tons
2000 CFM
5 Tons
2000 CFM
1–1/2
600
ON
OFF
OFF
X
X
X
—
—
—
2
800
OFF
ON
OFF
X
X
X
X
X
X
2–1/2
1000
ON
ON
OFF
X
X
X
X
X
X
3
1200
OFF
OFF
ON
X
X
X
X
X
X
3–1/2
1400
ON
OFF
ON
X
X
X
X
X
X
4
1600
OFF
ON
ON
—
—
—
X
X
X
5
2000
ON
ON
ON
—
—
—
X
X
X
X–Indicates allowable selection.
Fig. 53—Example of Setup Switch in OFF Position
A95198
1
OFF
Fig. 54—Inducer Housing Drain Tube
A99118