Grayhill Modules AC Output User Manual

Ac output modules, Dimensions, Fuses

Advertising
background image

Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois 60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com

I/O Modules

AC Output Modules

FEATURES
• Transient Protection: Meets the

requirements of IEEE 472, “Surge
Withstanding Capability Test”

• SPST, Normally Open
• Zero Crossing Turn-On
• UL, CSA, CE, TÜV Certified
• Optical Isolation
• OpenLine

®

and G5 Modules

Provide Replaceable 5x20 mm
Glass Fuses

• Built-in Status LED
• Lifetime Warranty

Maximum Current Versus
Ambient Temperature
The chart indicates continuous current to limit
the junction temperatures to 100°C. Information
is based on steady state heat transfer in a 2
cubic foot sealed enclosure.

Figure 1

DIMENSIONS

For complete dimensional drawings, see pages
L-4 or L-5.

FUSES

G5 Fuses are 5 Amp Littelfuse part number
217005 or equivalent. OpenLine

®

fuses are

3.15 Amp Littelfuse part number 2173.15.

CIRCUITRY

70L-OAC

70G-OAC 70-OAC 70M-OAC

4

3

2

1

-40˚

-20˚

0

20˚

40˚

60˚

80˚

100˚

AMBIENT TEMPERATURE (˚C)

LOAD CURRENT (AMPS)

STANDARD, G5 PACKAGES

MINIATURE PACKAGE

OPENLINE PACKAGE/CH

Package Style

Std (70-)

Mini (70M-)

G5 (70G-)

OL (70L-)

Specifications

Units

Load Current Range

1

A rms

0.03 to 3.5

0.03 to 3.0

0.03 to 3.5

0.03 to 2.0/CH

Maximum 1 Cycle Surge

2

A rms

80

80

80

30

Maximum Turn-On-Time (60 Hz)

3

mSec

8.33

8.33

8.33

8.33

Maximum Turn-Off Time (60 Hz)

mSec

8.33

8.33

8.33

8.33

Static dv/dt

7

V/µsec

3000

3000

3000

3000

Typ. Power Dissipation

W/A

1.0

1.0

1.0

1.0

Isolation Voltage

4

V rms

4000

4000

4000

2500

Vibration

5

MIL-STD-202

MIL-STD-202

MIL-STD-202

IEC68-2-6

Mechanical Shock

6

MIL-STD-202

MIL-STD-202

MIL-STD-202

IEC68-2-27

Storage Temp. Range

°C

-40 to 125

-40 to 125

-40 to 125

-40 to 100

Operating Temp. Range

°C

-40 to 100

-40 to 100

-40 to 100

-40 to 85

Warranty

Lifetime

Lifetime

Lifetime

Lifetime

1

See Figure 1 for derating.

2

Maximum 10 cycle surge is 50% of 1 cycle surge. Application of maximum surge may not be repeated until module temperature has returned
to its steady state value.

3

Except 70-OAC5A5 which is 200 µSec and 70-OAC5A-11, 70M-OAC5A-11, and 70G-OAC5A-11 which are 100 µSec.

4

Field to logic and channel-to-channel if Grayhill racks are used.

5

MIL-STD-202, Method 204, 20 , 10-2000 Hz or IEC68-2-6, 0.15 mm/sec

2

, 10-150 Hz.

6

MIL-STD-202, Method 213, Condition F, 1500G or IEC68-2-27, 11 mS, 15g.

7

Except part numbers with -L suffix which have a dv/dt rating of 200 V/µSec.

SPECIFICATIONS: By Package Style

Standard, Mini, G5

OpenLine

®

1

2

3

4

Rx

VAC

DC CONTROL

TRIGGER

CIRCUIT

SNUBBER

LOAD

LOAD

+

Fuse and status LED in G5 and OpenLine modules only.

TYPICAL WIRING FOR MODULE 0

5

1

1

2

2

6

7

2.15K

MODULE

OPTICAL

ISOLATION

OPTICAL

ISOLATION

SNUBBER

SNUBBER

CHANNEL A

CHANNEL B

B

A

RACK

OR

BASE

LOAD

LOAD

3

3

4

4

TERMINAL
BLOCK #

I/O MODULE
PIN #

GND

Vcc

CH. A CONTROL

CH. B CONTROL

MODULE ID

I/O

6

Advertising