Grayhill Modules DC Output User Manual

Dc output modules, Circuitry dimensions, Fuses

Advertising
background image

Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois 60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com

I/O Modules

70L-ODC

70G-ODC 70-ODC 70M-ODC

CIRCUITRY

DIMENSIONS

For complete dimensional drawings, see pages
L-4 or L-5.

FUSES

G5 Fuses are 5 Amp Littelfuse part number
217005 or equivalent. OpenLine

®

fuses are

3.15 Amp Littelfuse part number 2173.15.

Fuse kits available, see page L-104.

DC Output Modules

FEATURES
• Transient Protection: Meets the

requirements of IEEE 472, "Surge
Withstanding Capability Test"

• SPST, Normally Open
• UL, CSA, CE, TÜV Certified
• Optical Isolation
• OpenLine

®

and G5 Modules

Provide Replaceable 5x20mm
Glass Fuses

• Built-in Status LED
• Lifetime Warranty

Figure 1

Maximum Current Versus
Ambient Temperature
The chart indicates continuous current to limit
the junction temperatures to 115°C. Information
is based on steady state heat transfer in a 2
cubic foot sealed enclosure.

4

3

2

1

-40˚

-20˚

0

20˚

40˚

60˚

80˚

100˚

AMBIENT TEMPERATURE (˚C)

LOAD CURRENT (AMPS)

STANDARD, G5 PACKAGES

MINIATURE PACKAGE

OPENLINE PACKAGE/CH

200 VDC STYLE

Package Style

Std (70-)

Mini (70M-)

G5 (70G-)

OL (70L-)

Specifications

Units

Load Current Range

1

A

0.02-3.5

0.02-3.0

0.02-3.5

0.02-2.0/CH

Surge Current for 1 Sec.

A

5

5

5

5

Maximum Reverse Logic Voltage

Vdc

-5

-5

-5

-5

Isolation Voltage

2

Vrms

4000

4000

4000

2500

Vibration

3

MIL-STD-202

MIL-STD-202

MIL-STD-202

IEC68-2-6

Mechanical Shock

4

MIL-STD-202

MIL-STD-202

MIL-STD-202

IEC68-2-27

Storage Temp. Range

°C

-40 to 125

-40 to 125

-40 to 125

-40 to 100

Operating Temp. Range

°C

-40 to 100

-40 to 100

-40 to 100

-40 to 85

Warranty

Lifetime

Lifetime

Lifetime

Lifetime

1

See Figure 1 for derating.

2

Field to logic and channel-to-channel if Grayhill racks are used.

3

MIL-STD-202, Method 204, 20 G, 10-2000 Hz or IEC68-2-6, 0.15 mm/sec

2

, 10-150 Hz.

4

MIL-STD-202, Method 213, Condition F, 1500 G or IEC68-2-27, 11 mS, 15g.

SPECIFICATIONS: By Package Style

Standard, Mini, G5

OpenLine

®

1

2

3

4

Rx

VDC

DC CONTROL

VOLTAGE

SPIKE

PROTECTION

LOAD

LOAD

DRIVER

CIRCUIT

+

+

Fuse and status LED in G5 and OpenLine modules only.

TYPICAL WIRING FOR MODULE 0

2.15K

B

A

OPTICAL

ISOLATION

OPTICAL

ISOLATION

DRIVER

CIRCUIT

DRIVER

CIRCUIT

CHANNEL A

CHANNEL B

BASE

OR

RACK

I/O MODULE
PIN #

TERMINAL
BLOCK #

LOAD

DC

SUPPLY

DC

SUPPLY

LOAD

+

+

1

2

3

4

1

2

3

4

5

6

7

8

9

GND

Vcc

CH. A

CONTROL

CH. B

CONTROL

MODULE ID

I/O

8