1. Functions of the EDS 300

Depending on the model, the unit offers the following functions:

•

Display of the actual pressure, maximum value or a switching point.

•

Switching the switching outputs according to the pressure and the pre-set switching
parameters.

•

Analogue output

•

Menu for basic settings (adapting the EDS 300 to the particular application)

•

Two different types of programming enable

Three different output models are available:

•

EDS 300 with 1 switching output (1.2 A load capacity, no analogue output)

•

EDS 300 with 2 switching outputs (1.2 A load capacity, no analogue output)

•

EDS 300 with 1 switching output (1.2 A load capacity) and 1 analogue output (4...20 mA)

2. Mounting

The EDS 300 can be mounted directly onto a hydraulic block via the pressure connection
(7/16 SAE 4 female).
When used in critical applications (e.g. strong vibrations or knocks) the pressure connection
must be mechanically decoupled via a Minimess hose. Mounting clamps are available as an
accessory (see point 12.2 "Accessories - for mechanical connection").
The electrical connection should be carried out by a qualified electrician according to the
relevant regulations of the country concerned (VDE 0100 in Germany). The pressure switch
housing must be earthed properly at the same time. When fitted into a hydraulic block it is
sufficient if the block is earthed via the hydraulic system. In the case of Minimess hose-
mounting, the housing must be earthed separately.
Additional assembly notes which, from experience, reduce the effect of electromagnetic
interference:

•

Make line connections as short as possible.

•

Use screened lines (e.g. LIYCY 4 x 0.5 mm2)

•

The cable screening must be fitted by qualified personnel subject to the ambient
conditions and with the aim of suppressing interference.

•

Direct proximity to connecting lines of user units or electrical or electronic units causing
interference must be avoided as far as possible.

3. Operating keys on the membrane keypad

4-digit

keys for setting switching

digital display

additional functions

HYDAC

EDS 300

SP1

SP2

mode

points, switch-back points and

PSI

4. Digital display