Receptacles, Generator adapter cord set, Stopping the engine – Briggs & Stratton 30246 User Manual

Page 10: Caution

Advertising
background image

OPERATION

10

Stopping the Engine

1.

Turn OFF and unplug all electrical loads from generator
panel receptacles. NEVER start or stop engine with
electrical devices plugged in and turned ON.

2.

Let engine run at no-load for several minutes to
stabilize internal temperatures of engine and generator.

3.

Turn engine off according to instructions given in the
engine owner’s manual.

4.

Move fuel valve to “Off” position.

RECEPTACLES

120/240 Volt AC, 30 Amp, Locking

Receptacle

Use a NEMA L14–30 plug with this receptacle. Connect a
4–wire cord set rated for 250 Volt AC loads at 30 Amps (or
greater) (Figure 5).You can use the same 4–wire cord if you
plan to run a 120 Volt load.

This receptacle powers 120/240 Volt AC, 60 Hz, single
phase loads requiring up to 5,550 watts of power
(5.55 kW) at 23.1 Amps for 240 Volts or two independent
120 Volt loads at 23.1 Amps each.The outlet is protected
by a push–to–reset circuit breaker.

120 Volt AC, 20 Amp, Duplex

Receptacles

Each duplex receptacle (Figure 6) is protected against
overload by a push–to–reset circuit breaker.

Use each receptacle to operate 120 Volt AC, single–phase,
60 Hz electrical loads requiring up to 2,400 watts (2.4 kW)
at 20 Amps of current. Use cord sets that are rated for
125 Volt AC loads at 20 Amps (or greater).

GENERATOR ADAPTER

CORD SET

The generator is equipped with a 25’ generator adapter cord
set designed for a 240 Volt, 30 Amp grounded neutral circuit
(Figure 7).The generator adapter cord set provides a
convenient supply of emergency power into your dwelling so
that your generator can be operated safely outside.

The maximum load on each outlet is 20 Amps.The
maximum total load on both yellow wire outlets or black
wire outlets is 30 Amps.

NOTE: Follow all safety precautions when connecting any
extension cord or device to the generator.

Figure 6 — 120 Volt, 20 Amp Duplex Receptacle

• NEVER attempt to power a device requiring more amperage

than generator or receptacle can supply.

• DO NOT overload the generator. See “Don’t Overload

Generator”.

Receptacles may be marked with rating value greater
than generator output capacity.

CAUTION

Figure 5 — 120/240 Volt AC, 30 Amp Receptacle

4-Wire Cord Set

240V

120V

120V

W (Neutral)

X (Hot)

Y (Hot)

NEMA L14-30

Ground (Green)

Figure 7 — Generator Adapter Cord Set

Advertising