3 can port, Can port, Electrical installation – Lenze p300 Operating Instructions User Manual

Page 31: Stop

Advertising
background image

Electrical installation

Interfaces for peripheral devices

CAN port

6

31

Lenze ¯ BA_p300 ¯ 2.0

6.4.3

CAN port

Figure

Connection

Connection type

Cable type

X5:
CAN bus connection
Pin 1: CAN−GND (CG)
Pin 2: CAN−LOW (LO)
Pin 3: not assigned
Pin 4: CAN−HIGH (HI)
Pin 5: not assigned

5−pole Phoenix

Combicon socket

CAN cable complying with

ISO 11898−2 with Phoenix

Combicon plug, MSTB 2.5 /

5−STF−5.8

EL100−011

Specification of the bus cable

We recommend using CAN cables complying with ISO 11898−2:

CAN cable complying with ISO 11898−2
Cable type

Paired with shielding

Impedance

120

W (95 ... 140 W)

Cable resistance/cross−section

Cable length

£ 300 m £ 70 mW/m / 0.25 … 0.34 mm

2

(AWG22)

Cable length 301 … 1000 m

£ 40 mW/m / 0.5 mm

2

(AWG20)

Signal propagation delay

£ 5 ns/m

Connection plan

(

Stop!

Connect a 120

W terminating resistor to the first and last bus device.

CG

CAN

LO HI

CG

CAN

LO HI

CG

CAN

LO HI

R

R

A

n

A

2

A

1

EL100−009

Fig. 6−2

Connection plan for the CAN bus

A1

Node 1

A2

Node 2

An

Node n

CG

CAN−GND

LO

CAN−LOW

HI

CAN−HIGH

R

120

W−bus terminating resistor

Shielding

EL100−033

Fig. 6−3

CAN cable shield connection via cable clamp in the control cabinet