2.5.3 Preparation of cables

• Gut cable to lcngth at right anglas an a rigid base using a sharp

knite.

Be aura to usa a good as naw blade (e.g. utility knife)

Remove 20 mm ot the rad PUR sheath, it presont.

Poliah ond ot tibre optic cable (grain

=

Pl 000).

Note:

With unpolishad tibre-optic Cable ends, the maximum Cable
langth is typically reducad by 13 m (sf150 dB/km).

A spetial )ibra-optic connector is not raquired.

2.5.4 Connectlon

Insert tibre-optic

cable end info tha tranamitter or receivar

houaing as far as posaible.

• Tighten ptnch screw joint cautiously.

2.5.5 Assembly

• Gonneet tha white fibre-optic adaptor connactor (trransmittar,

ToD) ot the master computer to the black tibre-optic adaptor

connector (recaiver,

RaD) ot Ihe cuntroller by using a plastic

fibre-optic cable.

• Connect the white tibra-optic adaptor connector (tranamitter,

ToD) ot the controller to tho black tibre-optic adaptor connector
(receiver, RxD> ot tho noxt controller, etc.

• Connect the white fibre-optic adaptor connactor (tranamitter,

ToD> ot tha last controller to tha black tibre-optic adaptor
connector (recetver, RxD) ot the master computer.

Wheri using tha tibre-optic distributor, please act corraapondingly

(see fig. 2.3.2).

Note:

__

Banding radius should ha at least 30 mm.