Specifications–Model 494.47 Dual UART/Encoder Card

SSI duty-cycle settings

Older versions of the Model 494.47 and Model 494.49 cards used a fixed
25% low/75% high duty cycle for the SSI clock. To support other types of
SSI encoders, newer versions of these cards will set the duty cycle based on
the SSI baud rate setting. With the new design:

SSI baud rates less than or equal to 115.74 kHz = 50/50 duty cycle.

SSI baud rates greater than 115.74 kHz = 25/75 duty cycle.

The revisions listed in the following table include the SSI duty-cycle
changes described above. Cards that have the programmable-logic-device
revision listed in the table will support the 50/50 duty cycle.

P

ARAMETER

S

PECIFICATION

Encoder Interface

RS-485

UART Electrical Interface

RS-485 (2 or 4 wire)

UART Baud Rate

300 to 57600 Baud (software configurable)

Power Out
(to device)

15 V DC, Poly fused at 200 mA (continuous
current) and 400 mA (trip current)

Supported Encoder/Digital
Transducer Interfaces

You can use system hardware-mapping
software to select the type of interface:

SSI (Temposonics R)

Gurley (Teledyne)

Incremental/Velocity (includes counter selection)

PWM (Temposonics G)

E

NCODER

C

ARD

P

ROGRAMMABLE

L

OGIC

D

EVICE

R

EVISION

Model 494.47

H or higher

Model 494.49

C or higher