MTS FlexTest® Models 40/60/100/200 Controller Hardware

Model 493.74 Two-Station HSM Interface Board

Digital I/O and Transition Boards

252

Station stop

The Emergency Stop connection can also be configured as a station stop.
When this is done, be sure that you have other Emergency Stop boxes near
by. Pressing Station Stop will shut down the hydraulics to an individual
station without shutting down power to the hydraulic power unit.

Note

A Model 493.73 HPU Transition Board must be installed for the
Emergency Stop connection to be enabled.

J43 Interlock Connections for the Model 493.74 HSM Board

Connector J43 Interlock provides two optically isolated inputs that can
initiate interlocks. Input 1 initiates a station interlock. Input 2 initiates a
program interlock. Both inputs can accept relay-contact or logic-signal
inputs.

Note

If only one contact is used, the other contact must be jumpered.

Input 1

Station

Interlock

Input 2

Program

Interlock

1

2

3

4

5

6

7

8

J43

Intlk

+24 V

From

External Device

+24 V

0 V

493.74 HSM Board

J43-2

J43-1

Intlk

J28B HSM

R

J43-1

J43-2

Run/Stop

J44-1

J44-2

Aux Power

J49-1

J49-2

Load Frame

J29-1

J29-2

J28A HSM

493.74

HSM

Station

Logic

Input

Relay

Contacts