Cable specification – MTS FlexTest Models 200 User Manual

Page 66

Advertising
background image

MTS FlexTest® Models 40/60/100/200 Controller Hardware

Model 494.41 Single-Station System Board

FlexTest Controller Configurations

66

UPS Connections for the Model 494.41 System Board (FT40)

The following drawing shows UPS connections for the Model 494.41 System
board. Once connected, use your controller software to add the digital input
resources and configure the digital inputs to perform various actions in response
to the UPS signals.

Note

See your controller software user guide for information on how digital
inputs are assigned and used.

Cable specification

To maintain EMC compliance, the J54 Digital Input cable must comply with the
following specifications:

Connector type–9-pin contact, type D, male EMI connector.

Back shell–EMI metallized plastic or metal.

Cable—26 to 22 AWG, 4-conductor with an overall braided shield that is
connected to the backshell at the chassis.

494.41 System I/O Board

Power

100-240 VAC

50-60 Hz, 1-2 A

DA Output

J24

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8

J54 Dig In

J49

Aux Pwr

J25 Hpu

Dig Out J55

Intlk J43

E-stop J29

J28 HSM

LAN 2

LAN 1

DEBUG

MOT

O

ROLA

10/100 BASE T 10/100 BASE T

SCSI

BUSY

PIB

BUSY

PCI MEZZANINE CARD

PCI MEZZANINE CARD

J54 Digital Input

+24 V DC

UPS

AC Fail Contacts

Open = Logic 0

1

2

3

8

4

5

J54

Dig In

Digital Input 1

Low Battery Contacts

Open = Logic 0

Digital Input 2

Advertising